AEMCMK-HF / AXQJ-EMC / IFSI-EMC-Al
Download product group datasheet
Aluminium power cable for fixed installations indoors and outdoors. May be buried directly in soil. EMC shielded cable gives an excellent protection against electromagnetic disturbancies. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Dca-s2,d2,a2.
Standards | SFS 5546, SEK TS 424 14 18-1, HD 604 5 I & D, IEC 60502-1 |
---|---|
Reaction to fire | Dca-s2,d2,a2 |
CPR - DoP | 2024009_DOP.pdf 2021005_DOP.pdf |
Conductor | 16-25 mm² circular stranded aluminium, EN/IEC 60228 class 2 35-300 mm² sector shaped stranded aluminium, EN/IEC 60228 class 2 |
Insulation | Cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | Brown, black, grey Blue, brown, black, grey |
Inner covering | Plastic tape |
Metal screen | EMC-copper foil and copper wires |
Oversheath | UV-protected polyolefin compound |
Colour of the oversheath | Black |
3x16/10
Electric number
Size
Packaging
Voltage
3x16/10
Nominal diameter of complete cable mm
21
Nominal weight of cable kg/km
613
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
10
During handling and installation, cable cm
25
In final installation, phase conductor cm
7
In final installation, cable cm
17
During handling and installation, cable m
0.25
In final installation, cable m
0.17
Max. pulling force
Pulling-eye kN
0.7
Pulling-stocking kN
0.7
Resistance 20 °C Ω/km
1,91
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176225653
Reka code
1149200
3x120/41
Electric number
Size
Packaging
Voltage
3x120/41
Nominal diameter of complete cable mm
36
Nominal weight of cable kg/km
1977
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
31
During handling and installation, cable cm
43
In final installation, phase conductor cm
22
In final installation, cable cm
30
During handling and installation, cable m
0.43
In final installation, cable m
0.3
Max. pulling force
Pulling-eye kN
5.4
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176225776
Reka code
1149206
3x185/57
Electric number
Size
Packaging
Voltage
3x185/57
Nominal diameter of complete cable mm
44
Nominal weight of cable kg/km
2882
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
38
During handling and installation, cable cm
53
In final installation, phase conductor cm
27
In final installation, cable cm
37
During handling and installation, cable m
0.53
In final installation, cable m
0.37
Max. pulling force
Pulling-eye kN
8.3
Pulling-stocking kN
8.3
Resistance 20 °C Ω/km
0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,320
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176225813
Reka code
1149208
3x240/72
Electric number
Size
Packaging
Voltage
3x240/72
Nominal diameter of complete cable mm
48
Nominal weight of cable kg/km
3660
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
43
During handling and installation, cable cm
58
In final installation, phase conductor cm
30
In final installation, cable cm
40
During handling and installation, cable m
0.58
In final installation, cable m
0.4
Max. pulling force
Pulling-eye kN
10.8
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,253
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176225837
Reka code
1149209
4x16/10
Electric number
Size
Packaging
Voltage
4x16/10
Nominal diameter of complete cable mm
22
Nominal weight of cable kg/km
709
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
10
During handling and installation, cable cm
27
In final installation, phase conductor cm
7
In final installation, cable cm
19
During handling and installation, cable m
0.27
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
1
Pulling-stocking kN
1
Resistance 20 °C Ω/km
1,91
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176225875
Reka code
1149214
4x25/16
Electric number
Size
Packaging
Voltage
4x25/16
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1003
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
9
During handling and installation, cable cm
31
In final installation, phase conductor cm
6
In final installation, cable cm
22
During handling and installation, cable m
0.31
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
1.5
Pulling-stocking kN
1.5
Resistance 20 °C Ω/km
1,20
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176225899
Reka code
1149215
4x35/16
Electric number
Size
Packaging
Voltage
4x35/16
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
859
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
16
During handling and installation, cable cm
29
In final installation, phase conductor cm
11
In final installation, cable cm
20
During handling and installation, cable m
0.29
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.1
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176225912
Reka code
1149216
4x70/21
Electric number
Size
Packaging
Voltage
4x70/21
Nominal diameter of complete cable mm
31
Nominal weight of cable kg/km
1464
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
23
During handling and installation, cable cm
37
In final installation, phase conductor cm
16
In final installation, cable cm
26
During handling and installation, cable m
0.38
In final installation, cable m
0.26
Max. pulling force
Pulling-eye kN
4.2
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176225950
Reka code
1149218
4x120/41
Electric number
Size
Packaging
Voltage
4x120/41
Nominal diameter of complete cable mm
40
Nominal weight of cable kg/km
2425
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
29
During handling and installation, cable cm
48
In final installation, phase conductor cm
20
In final installation, cable cm
34
During handling and installation, cable m
0.48
In final installation, cable m
0.34
Max. pulling force
Pulling-eye kN
7.2
Pulling-stocking kN
7.2
Resistance 20 °C Ω/km
0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176225998
Reka code
1149220
4x150/41
Electric number
Size
Packaging
Voltage
4x150/41
Nominal diameter of complete cable mm
45
Nominal weight of cable kg/km
2875
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
32
During handling and installation, cable cm
54
In final installation, phase conductor cm
23
In final installation, cable cm
37
During handling and installation, cable m
0.54
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
9
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176226018
Reka code
1149221
4x300/88
Electric number
Size
Packaging
Voltage
4x300/88
Nominal diameter of complete cable mm
60
Nominal weight of cable kg/km
5554
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
1.8
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
46
During handling and installation, cable cm
72
In final installation, phase conductor cm
32
In final installation, cable cm
50
During handling and installation, cable m
0.72
In final installation, cable m
0.5
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,206
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176226070
Reka code