AEMCMK-HF C / AXQJ C / IFSI-EMC-Al C

Download product group datasheet

Aluminium power cable for fixed installations indoors and outdoors. May be buried directly in soil. Can also be used in medical facilities where higher fire class is required. EMC shielded cable gives an excellent protection against electromagnetic disturbancies. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Cca-s1,d1,a1.

Standards SFS 5546, SEK TS 424 14 18-1, HD 604 5 I & D, IEC 60502-1
Reaction to fire Cca-s1,d1,a1
CPR - DoP 2019002_DOP.pdf
Conductor Sector shaped, stranded aluminium, EN/IEC 60228 class 2
Insulation Cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Brown, black, grey
Blue, brown, black, grey
Inner covering Plastic tape
Metal screen EMC-copper foil and copper wires
Oversheath UV-protected polyolefin compound
Colour of the oversheath Black

3x35/16

Electric number Size Packaging Voltage

3x35/16

Nominal diameter of complete cable mm 22
Nominal weight of cable kg/km 726
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 17
During handling and installation, cable cm 27
In final installation, phase conductor cm 12
In final installation, cable cm 19
During handling and installation, cable m 0.27
In final installation, cable m 0.19
Max. pulling force
Pulling-eye kN 1.6
Pulling-stocking kN 1.6
Resistance 20 °C Ω/km 0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302682
Reka code 1149282
Nominal diameter of complete cable mm 22
Nominal weight of cable kg/km 726
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 17
During handling and installation, cable cm 27
In final installation, phase conductor cm 12
In final installation, cable cm 19
During handling and installation, cable m 0.27
In final installation, cable m 0.19
Max. pulling force
Pulling-eye kN 1.6
Pulling-stocking kN 1.6
Resistance 20 °C Ω/km 0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302675
Reka code 1149282

3x50/16

Electric number Size Packaging Voltage

3x50/16

Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 866
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 20
During handling and installation, cable cm 28
In final installation, phase conductor cm 14
In final installation, cable cm 20
During handling and installation, cable m 0.28
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 2.3
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302712
Reka code 1149283
Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 866
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 20
During handling and installation, cable cm 28
In final installation, phase conductor cm 14
In final installation, cable cm 20
During handling and installation, cable m 0.28
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 2.3
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302705
Reka code 1149283

3x70/21

Electric number Size Packaging Voltage

3x70/21

Nominal diameter of complete cable mm 27
Nominal weight of cable kg/km 1175
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 24
During handling and installation, cable cm 33
In final installation, phase conductor cm 17
In final installation, cable cm 23
During handling and installation, cable m 0.33
In final installation, cable m 0.23
Max. pulling force
Pulling-eye kN 3.2
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,868
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302736
Reka code 1149284
Nominal diameter of complete cable mm 27
Nominal weight of cable kg/km 1175
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 24
During handling and installation, cable cm 33
In final installation, phase conductor cm 17
In final installation, cable cm 23
During handling and installation, cable m 0.33
In final installation, cable m 0.23
Max. pulling force
Pulling-eye kN 3.2
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,868
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302743
Reka code 1149284

3x95/29

Electric number Size Packaging Voltage

3x95/29

Nominal diameter of complete cable mm 32
Nominal weight of cable kg/km 1539
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 27
During handling and installation, cable cm 38
In final installation, phase conductor cm 19
In final installation, cable cm 27
During handling and installation, cable m 0.38
In final installation, cable m 0.27
Max. pulling force
Pulling-eye kN 4.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,641
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302774
Reka code 1149285
Nominal diameter of complete cable mm 32
Nominal weight of cable kg/km 1539
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 27
During handling and installation, cable cm 38
In final installation, phase conductor cm 19
In final installation, cable cm 27
During handling and installation, cable m 0.38
In final installation, cable m 0.27
Max. pulling force
Pulling-eye kN 4.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,641
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302767
Reka code 1149285

3x120/41

Electric number Size Packaging Voltage

3x120/41

Nominal diameter of complete cable mm 36
Nominal weight of cable kg/km 1987
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 31
During handling and installation, cable cm 43
In final installation, phase conductor cm 22
In final installation, cable cm 30
During handling and installation, cable m 0.43
In final installation, cable m 0.3
Max. pulling force
Pulling-eye kN 5.4
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302798
Reka code 1149286
Nominal diameter of complete cable mm 36
Nominal weight of cable kg/km 1987
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 31
During handling and installation, cable cm 43
In final installation, phase conductor cm 22
In final installation, cable cm 30
During handling and installation, cable m 0.43
In final installation, cable m 0.3
Max. pulling force
Pulling-eye kN 5.4
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302804
Reka code 1149286

3x150/41

Electric number Size Packaging Voltage

3x150/41

Nominal diameter of complete cable mm 39
Nominal weight of cable kg/km 2315
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 35
During handling and installation, cable cm 47
In final installation, phase conductor cm 24
In final installation, cable cm 33
During handling and installation, cable m 0.47
In final installation, cable m 0.33
Max. pulling force
Pulling-eye kN 6.8
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302835
Reka code 1149287
Nominal diameter of complete cable mm 39
Nominal weight of cable kg/km 2315
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 35
During handling and installation, cable cm 47
In final installation, phase conductor cm 24
In final installation, cable cm 33
During handling and installation, cable m 0.47
In final installation, cable m 0.33
Max. pulling force
Pulling-eye kN 6.8
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302828
Reka code 1149287

3x185/57

Electric number Size Packaging Voltage

3x185/57

Nominal diameter of complete cable mm 44
Nominal weight of cable kg/km 2895
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 38
During handling and installation, cable cm 53
In final installation, phase conductor cm 27
In final installation, cable cm 37
During handling and installation, cable m 0.53
In final installation, cable m 0.37
Max. pulling force
Pulling-eye kN 8.3
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,320
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302859
Reka code 1149288
Nominal diameter of complete cable mm 44
Nominal weight of cable kg/km 2895
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 38
During handling and installation, cable cm 53
In final installation, phase conductor cm 27
In final installation, cable cm 37
During handling and installation, cable m 0.53
In final installation, cable m 0.37
Max. pulling force
Pulling-eye kN 8.3
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,320
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302866
Reka code 1149288

3x240/72

Electric number Size Packaging Voltage

3x240/72

Nominal diameter of complete cable mm 48
Nominal weight of cable kg/km 3675
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 43
During handling and installation, cable cm 58
In final installation, phase conductor cm 30
In final installation, cable cm 40
During handling and installation, cable m 0.58
In final installation, cable m 0.4
Max. pulling force
Pulling-eye kN 10.8
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,253
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302897
Reka code 1149289
Nominal diameter of complete cable mm 48
Nominal weight of cable kg/km 3675
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 43
During handling and installation, cable cm 58
In final installation, phase conductor cm 30
In final installation, cable cm 40
During handling and installation, cable m 0.58
In final installation, cable m 0.4
Max. pulling force
Pulling-eye kN 10.8
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,253
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302880
Reka code 1149289

3x300/88

Electric number Size Packaging Voltage

3x300/88

Nominal diameter of complete cable mm 56
Nominal weight of cable kg/km 4560
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 50
During handling and installation, cable cm 67
In final installation, phase conductor cm 35
In final installation, cable cm 47
During handling and installation, cable m 0.67
In final installation, cable m 0.47
Max. pulling force
Pulling-eye kN 13.5
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,206
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302927
Reka code 1149290
Nominal diameter of complete cable mm 56
Nominal weight of cable kg/km 4560
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 50
During handling and installation, cable cm 67
In final installation, phase conductor cm 35
In final installation, cable cm 47
During handling and installation, cable m 0.67
In final installation, cable m 0.47
Max. pulling force
Pulling-eye kN 13.5
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,206
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302910
Reka code 1149290

4x35/16

Electric number Size Packaging Voltage

4x35/16

Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 864
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 16
During handling and installation, cable cm 29
In final installation, phase conductor cm 11
In final installation, cable cm 20
During handling and installation, cable m 0.29
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 2.1
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302958
Reka code 1149294
Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 864
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 16
During handling and installation, cable cm 29
In final installation, phase conductor cm 11
In final installation, cable cm 20
During handling and installation, cable m 0.29
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 2.1
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302941
Reka code 1149294

4x50/16

Electric number Size Packaging Voltage

4x50/16

Nominal diameter of complete cable mm 28
Nominal weight of cable kg/km 1089
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 19
During handling and installation, cable cm 34
In final installation, phase conductor cm 13
In final installation, cable cm 23
During handling and installation, cable m 0.34
In final installation, cable m 0.23
Max. pulling force
Pulling-eye kN 3
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302989
Reka code 1149295
Nominal diameter of complete cable mm 28
Nominal weight of cable kg/km 1089
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 19
During handling and installation, cable cm 34
In final installation, phase conductor cm 13
In final installation, cable cm 23
During handling and installation, cable m 0.34
In final installation, cable m 0.23
Max. pulling force
Pulling-eye kN 3
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302972
Reka code 1149295

4x70/21

Electric number Size Packaging Voltage

4x70/21

Nominal diameter of complete cable mm 31
Nominal weight of cable kg/km 1471
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 23
During handling and installation, cable cm 38
In final installation, phase conductor cm 16
In final installation, cable cm 26
During handling and installation, cable m 0.38
In final installation, cable m 0.26
Max. pulling force
Pulling-eye kN 4.2
Pulling-stocking kN 4.2
Resistance 20 °C Ω/km 0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,868
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303016
Reka code 1149296
Nominal diameter of complete cable mm 31
Nominal weight of cable kg/km 1471
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 23
During handling and installation, cable cm 38
In final installation, phase conductor cm 16
In final installation, cable cm 26
During handling and installation, cable m 0.38
In final installation, cable m 0.26
Max. pulling force
Pulling-eye kN 4.2
Pulling-stocking kN 4.2
Resistance 20 °C Ω/km 0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,868
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303009
Reka code 1149296

4x95/29

Electric number Size Packaging Voltage

4x95/29

Nominal diameter of complete cable mm 35
Nominal weight of cable kg/km 1905
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 26
During handling and installation, cable cm 42
In final installation, phase conductor cm 18
In final installation, cable cm 30
During handling and installation, cable m 0.42
In final installation, cable m 0.3
Max. pulling force
Pulling-eye kN 5.7
Pulling-stocking kN 5.7
Resistance 20 °C Ω/km 0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,641
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303030
Reka code 1149297
Nominal diameter of complete cable mm 35
Nominal weight of cable kg/km 1905
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 26
During handling and installation, cable cm 42
In final installation, phase conductor cm 18
In final installation, cable cm 30
During handling and installation, cable m 0.42
In final installation, cable m 0.3
Max. pulling force
Pulling-eye kN 5.7
Pulling-stocking kN 5.7
Resistance 20 °C Ω/km 0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,641
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303047
Reka code 1149297

4x120/41

Electric number Size Packaging Voltage

4x120/41

Nominal diameter of complete cable mm 40
Nominal weight of cable kg/km 2428
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 29
During handling and installation, cable cm 49
In final installation, phase conductor cm 20
In final installation, cable cm 34
During handling and installation, cable m 0.49
In final installation, cable m 0.34
Max. pulling force
Pulling-eye kN 7.2
Pulling-stocking kN 7.2
Resistance 20 °C Ω/km 0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303078
Reka code 1149298
Nominal diameter of complete cable mm 40
Nominal weight of cable kg/km 2428
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 29
During handling and installation, cable cm 49
In final installation, phase conductor cm 20
In final installation, cable cm 34
During handling and installation, cable m 0.49
In final installation, cable m 0.34
Max. pulling force
Pulling-eye kN 7.2
Pulling-stocking kN 7.2
Resistance 20 °C Ω/km 0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303061
Reka code 1149298

4x150/41

Electric number Size Packaging Voltage

4x150/41

Nominal diameter of complete cable mm 45
Nominal weight of cable kg/km 2898
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 32
During handling and installation, cable cm 54
In final installation, phase conductor cm 23
In final installation, cable cm 38
During handling and installation, cable m 0.54
In final installation, cable m 0.38
Max. pulling force
Pulling-eye kN 9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303108
Reka code 1149299
Nominal diameter of complete cable mm 45
Nominal weight of cable kg/km 2898
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 32
During handling and installation, cable cm 54
In final installation, phase conductor cm 23
In final installation, cable cm 38
During handling and installation, cable m 0.54
In final installation, cable m 0.38
Max. pulling force
Pulling-eye kN 9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303092
Reka code 1149299

4x185/57

Electric number Size Packaging Voltage

4x185/57

Nominal diameter of complete cable mm 49
Nominal weight of cable kg/km 3572
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 37
During handling and installation, cable cm 59
In final installation, phase conductor cm 26
In final installation, cable cm 41
During handling and installation, cable m 0.59
In final installation, cable m 0.41
Max. pulling force
Pulling-eye kN 11.1
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,320
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303139
Reka code 1149300
Nominal diameter of complete cable mm 49
Nominal weight of cable kg/km 3572
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 37
During handling and installation, cable cm 59
In final installation, phase conductor cm 26
In final installation, cable cm 41
During handling and installation, cable m 0.59
In final installation, cable m 0.41
Max. pulling force
Pulling-eye kN 11.1
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,320
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303122
Reka code 1149300

4x240/72

Electric number Size Packaging Voltage

4x240/72

Nominal diameter of complete cable mm 56
Nominal weight of cable kg/km 4633
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 43
During handling and installation, cable cm 67
In final installation, phase conductor cm 30
In final installation, cable cm 47
During handling and installation, cable m 0.67
In final installation, cable m 0.47
Max. pulling force
Pulling-eye kN 14.4
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,253
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303160
Reka code 1149301
Nominal diameter of complete cable mm 56
Nominal weight of cable kg/km 4633
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 43
During handling and installation, cable cm 67
In final installation, phase conductor cm 30
In final installation, cable cm 47
During handling and installation, cable m 0.67
In final installation, cable m 0.47
Max. pulling force
Pulling-eye kN 14.4
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,253
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303153
Reka code 1149301

4x300/88

Electric number Size Packaging Voltage

4x300/88

Nominal diameter of complete cable mm 60
Nominal weight of cable kg/km 5576
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 46
During handling and installation, cable cm 72
In final installation, phase conductor cm 32
In final installation, cable cm 50
During handling and installation, cable m 0.72
In final installation, cable m 0.5
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,206
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303191
Reka code 1149302
Nominal diameter of complete cable mm 60
Nominal weight of cable kg/km 5576
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 46
During handling and installation, cable cm 72
In final installation, phase conductor cm 32
In final installation, cable cm 50
During handling and installation, cable m 0.72
In final installation, cable m 0.5
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,206
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303184
Reka code 1149302