AEMCMK-HF C / AXQJ C / IFSI-EMC-Al C
Download product group datasheet
Aluminium power cable for fixed installations indoors and outdoors. May be buried directly in soil. Can also be used in medical facilities where higher fire class is required. EMC shielded cable gives an excellent protection against electromagnetic disturbancies. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Cca-s1,d1,a1.
Standards | SFS 5546, SEK TS 424 14 18-1, HD 604 5 I & D, IEC 60502-1 |
---|---|
Reaction to fire | Cca-s1,d1,a1 |
CPR - DoP | 2019002_DOP.pdf |
Conductor | Sector shaped, stranded aluminium, EN/IEC 60228 class 2 |
Insulation | Cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | Brown, black, grey Blue, brown, black, grey |
Inner covering | Plastic tape |
Metal screen | EMC-copper foil and copper wires |
Oversheath | UV-protected polyolefin compound |
Colour of the oversheath | Black |
3x35/16
Electric number
Size
Packaging
Voltage
3x35/16
Nominal diameter of complete cable mm
22
Nominal weight of cable kg/km
726
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
17
During handling and installation, cable cm
27
In final installation, phase conductor cm
12
In final installation, cable cm
19
During handling and installation, cable m
0.27
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
1.6
Pulling-stocking kN
1.6
Resistance 20 °C Ω/km
0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302682
Reka code
1149282
Nominal diameter of complete cable mm
22
Nominal weight of cable kg/km
726
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
17
During handling and installation, cable cm
27
In final installation, phase conductor cm
12
In final installation, cable cm
19
During handling and installation, cable m
0.27
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
1.6
Pulling-stocking kN
1.6
Resistance 20 °C Ω/km
0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302675
Reka code
1149282
3x50/16
Electric number
Size
Packaging
Voltage
3x50/16
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
866
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
20
During handling and installation, cable cm
28
In final installation, phase conductor cm
14
In final installation, cable cm
20
During handling and installation, cable m
0.28
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.3
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302712
Reka code
1149283
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
866
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
20
During handling and installation, cable cm
28
In final installation, phase conductor cm
14
In final installation, cable cm
20
During handling and installation, cable m
0.28
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.3
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302705
Reka code
1149283
3x70/21
Electric number
Size
Packaging
Voltage
3x70/21
Nominal diameter of complete cable mm
27
Nominal weight of cable kg/km
1175
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
24
During handling and installation, cable cm
33
In final installation, phase conductor cm
17
In final installation, cable cm
23
During handling and installation, cable m
0.33
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
3.2
Pulling-stocking kN
3.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302736
Reka code
1149284
Nominal diameter of complete cable mm
27
Nominal weight of cable kg/km
1175
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
24
During handling and installation, cable cm
33
In final installation, phase conductor cm
17
In final installation, cable cm
23
During handling and installation, cable m
0.33
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
3.2
Pulling-stocking kN
3.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302743
Reka code
1149284
3x95/29
Electric number
Size
Packaging
Voltage
3x95/29
Nominal diameter of complete cable mm
32
Nominal weight of cable kg/km
1539
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
27
During handling and installation, cable cm
38
In final installation, phase conductor cm
19
In final installation, cable cm
27
During handling and installation, cable m
0.38
In final installation, cable m
0.27
Max. pulling force
Pulling-eye kN
4.3
Pulling-stocking kN
4.3
Resistance 20 °C Ω/km
0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,641
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302774
Reka code
1149285
Nominal diameter of complete cable mm
32
Nominal weight of cable kg/km
1539
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
27
During handling and installation, cable cm
38
In final installation, phase conductor cm
19
In final installation, cable cm
27
During handling and installation, cable m
0.38
In final installation, cable m
0.27
Max. pulling force
Pulling-eye kN
4.3
Pulling-stocking kN
4.3
Resistance 20 °C Ω/km
0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,641
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302767
Reka code
1149285
3x120/41
Electric number
Size
Packaging
Voltage
3x120/41
Nominal diameter of complete cable mm
36
Nominal weight of cable kg/km
1987
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
31
During handling and installation, cable cm
43
In final installation, phase conductor cm
22
In final installation, cable cm
30
During handling and installation, cable m
0.43
In final installation, cable m
0.3
Max. pulling force
Pulling-eye kN
5.4
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302798
Reka code
1149286
Nominal diameter of complete cable mm
36
Nominal weight of cable kg/km
1987
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
31
During handling and installation, cable cm
43
In final installation, phase conductor cm
22
In final installation, cable cm
30
During handling and installation, cable m
0.43
In final installation, cable m
0.3
Max. pulling force
Pulling-eye kN
5.4
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302804
Reka code
1149286
3x150/41
Electric number
Size
Packaging
Voltage
3x150/41
Nominal diameter of complete cable mm
39
Nominal weight of cable kg/km
2315
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
35
During handling and installation, cable cm
47
In final installation, phase conductor cm
24
In final installation, cable cm
33
During handling and installation, cable m
0.47
In final installation, cable m
0.33
Max. pulling force
Pulling-eye kN
6.8
Pulling-stocking kN
6.8
Resistance 20 °C Ω/km
0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302835
Reka code
1149287
Nominal diameter of complete cable mm
39
Nominal weight of cable kg/km
2315
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
35
During handling and installation, cable cm
47
In final installation, phase conductor cm
24
In final installation, cable cm
33
During handling and installation, cable m
0.47
In final installation, cable m
0.33
Max. pulling force
Pulling-eye kN
6.8
Pulling-stocking kN
6.8
Resistance 20 °C Ω/km
0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302828
Reka code
1149287
3x185/57
Electric number
Size
Packaging
Voltage
3x185/57
Nominal diameter of complete cable mm
44
Nominal weight of cable kg/km
2895
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
38
During handling and installation, cable cm
53
In final installation, phase conductor cm
27
In final installation, cable cm
37
During handling and installation, cable m
0.53
In final installation, cable m
0.37
Max. pulling force
Pulling-eye kN
8.3
Pulling-stocking kN
8.3
Resistance 20 °C Ω/km
0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,320
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302859
Reka code
1149288
Nominal diameter of complete cable mm
44
Nominal weight of cable kg/km
2895
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
38
During handling and installation, cable cm
53
In final installation, phase conductor cm
27
In final installation, cable cm
37
During handling and installation, cable m
0.53
In final installation, cable m
0.37
Max. pulling force
Pulling-eye kN
8.3
Pulling-stocking kN
8.3
Resistance 20 °C Ω/km
0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,320
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302866
Reka code
1149288
3x240/72
Electric number
Size
Packaging
Voltage
3x240/72
Nominal diameter of complete cable mm
48
Nominal weight of cable kg/km
3675
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
43
During handling and installation, cable cm
58
In final installation, phase conductor cm
30
In final installation, cable cm
40
During handling and installation, cable m
0.58
In final installation, cable m
0.4
Max. pulling force
Pulling-eye kN
10.8
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,253
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302897
Reka code
1149289
Nominal diameter of complete cable mm
48
Nominal weight of cable kg/km
3675
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
43
During handling and installation, cable cm
58
In final installation, phase conductor cm
30
In final installation, cable cm
40
During handling and installation, cable m
0.58
In final installation, cable m
0.4
Max. pulling force
Pulling-eye kN
10.8
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,253
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302880
Reka code
1149289
3x300/88
Electric number
Size
Packaging
Voltage
3x300/88
Nominal diameter of complete cable mm
56
Nominal weight of cable kg/km
4560
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
1.8
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
50
During handling and installation, cable cm
67
In final installation, phase conductor cm
35
In final installation, cable cm
47
During handling and installation, cable m
0.67
In final installation, cable m
0.47
Max. pulling force
Pulling-eye kN
13.5
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,206
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302927
Reka code
1149290
Nominal diameter of complete cable mm
56
Nominal weight of cable kg/km
4560
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
1.8
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
50
During handling and installation, cable cm
67
In final installation, phase conductor cm
35
In final installation, cable cm
47
During handling and installation, cable m
0.67
In final installation, cable m
0.47
Max. pulling force
Pulling-eye kN
13.5
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,206
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302910
Reka code
1149290
4x35/16
Electric number
Size
Packaging
Voltage
4x35/16
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
864
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
16
During handling and installation, cable cm
29
In final installation, phase conductor cm
11
In final installation, cable cm
20
During handling and installation, cable m
0.29
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.1
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302958
Reka code
1149294
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
864
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
16
During handling and installation, cable cm
29
In final installation, phase conductor cm
11
In final installation, cable cm
20
During handling and installation, cable m
0.29
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.1
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302941
Reka code
1149294
4x50/16
Electric number
Size
Packaging
Voltage
4x50/16
Nominal diameter of complete cable mm
28
Nominal weight of cable kg/km
1089
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
19
During handling and installation, cable cm
34
In final installation, phase conductor cm
13
In final installation, cable cm
23
During handling and installation, cable m
0.34
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
3
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302989
Reka code
1149295
Nominal diameter of complete cable mm
28
Nominal weight of cable kg/km
1089
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
19
During handling and installation, cable cm
34
In final installation, phase conductor cm
13
In final installation, cable cm
23
During handling and installation, cable m
0.34
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
3
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302972
Reka code
1149295
4x70/21
Electric number
Size
Packaging
Voltage
4x70/21
Nominal diameter of complete cable mm
31
Nominal weight of cable kg/km
1471
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
23
During handling and installation, cable cm
38
In final installation, phase conductor cm
16
In final installation, cable cm
26
During handling and installation, cable m
0.38
In final installation, cable m
0.26
Max. pulling force
Pulling-eye kN
4.2
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303016
Reka code
1149296
Nominal diameter of complete cable mm
31
Nominal weight of cable kg/km
1471
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
23
During handling and installation, cable cm
38
In final installation, phase conductor cm
16
In final installation, cable cm
26
During handling and installation, cable m
0.38
In final installation, cable m
0.26
Max. pulling force
Pulling-eye kN
4.2
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303009
Reka code
1149296
4x95/29
Electric number
Size
Packaging
Voltage
4x95/29
Nominal diameter of complete cable mm
35
Nominal weight of cable kg/km
1905
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
26
During handling and installation, cable cm
42
In final installation, phase conductor cm
18
In final installation, cable cm
30
During handling and installation, cable m
0.42
In final installation, cable m
0.3
Max. pulling force
Pulling-eye kN
5.7
Pulling-stocking kN
5.7
Resistance 20 °C Ω/km
0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,641
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303030
Reka code
1149297
Nominal diameter of complete cable mm
35
Nominal weight of cable kg/km
1905
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
26
During handling and installation, cable cm
42
In final installation, phase conductor cm
18
In final installation, cable cm
30
During handling and installation, cable m
0.42
In final installation, cable m
0.3
Max. pulling force
Pulling-eye kN
5.7
Pulling-stocking kN
5.7
Resistance 20 °C Ω/km
0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,641
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303047
Reka code
1149297
4x120/41
Electric number
Size
Packaging
Voltage
4x120/41
Nominal diameter of complete cable mm
40
Nominal weight of cable kg/km
2428
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
29
During handling and installation, cable cm
49
In final installation, phase conductor cm
20
In final installation, cable cm
34
During handling and installation, cable m
0.49
In final installation, cable m
0.34
Max. pulling force
Pulling-eye kN
7.2
Pulling-stocking kN
7.2
Resistance 20 °C Ω/km
0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303078
Reka code
1149298
Nominal diameter of complete cable mm
40
Nominal weight of cable kg/km
2428
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
29
During handling and installation, cable cm
49
In final installation, phase conductor cm
20
In final installation, cable cm
34
During handling and installation, cable m
0.49
In final installation, cable m
0.34
Max. pulling force
Pulling-eye kN
7.2
Pulling-stocking kN
7.2
Resistance 20 °C Ω/km
0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303061
Reka code
1149298
4x150/41
Electric number
Size
Packaging
Voltage
4x150/41
Nominal diameter of complete cable mm
45
Nominal weight of cable kg/km
2898
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
32
During handling and installation, cable cm
54
In final installation, phase conductor cm
23
In final installation, cable cm
38
During handling and installation, cable m
0.54
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
9
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303108
Reka code
1149299
Nominal diameter of complete cable mm
45
Nominal weight of cable kg/km
2898
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
32
During handling and installation, cable cm
54
In final installation, phase conductor cm
23
In final installation, cable cm
38
During handling and installation, cable m
0.54
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
9
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303092
Reka code
1149299
4x185/57
Electric number
Size
Packaging
Voltage
4x185/57
Nominal diameter of complete cable mm
49
Nominal weight of cable kg/km
3572
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
37
During handling and installation, cable cm
59
In final installation, phase conductor cm
26
In final installation, cable cm
41
During handling and installation, cable m
0.59
In final installation, cable m
0.41
Max. pulling force
Pulling-eye kN
11.1
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,320
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303139
Reka code
1149300
Nominal diameter of complete cable mm
49
Nominal weight of cable kg/km
3572
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
37
During handling and installation, cable cm
59
In final installation, phase conductor cm
26
In final installation, cable cm
41
During handling and installation, cable m
0.59
In final installation, cable m
0.41
Max. pulling force
Pulling-eye kN
11.1
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,320
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303122
Reka code
1149300
4x240/72
Electric number
Size
Packaging
Voltage
4x240/72
Nominal diameter of complete cable mm
56
Nominal weight of cable kg/km
4633
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
43
During handling and installation, cable cm
67
In final installation, phase conductor cm
30
In final installation, cable cm
47
During handling and installation, cable m
0.67
In final installation, cable m
0.47
Max. pulling force
Pulling-eye kN
14.4
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,253
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303160
Reka code
1149301
Nominal diameter of complete cable mm
56
Nominal weight of cable kg/km
4633
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
43
During handling and installation, cable cm
67
In final installation, phase conductor cm
30
In final installation, cable cm
47
During handling and installation, cable m
0.67
In final installation, cable m
0.47
Max. pulling force
Pulling-eye kN
14.4
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,253
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303153
Reka code
1149301
4x300/88
Electric number
Size
Packaging
Voltage
4x300/88
Nominal diameter of complete cable mm
60
Nominal weight of cable kg/km
5576
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
1.8
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
46
During handling and installation, cable cm
72
In final installation, phase conductor cm
32
In final installation, cable cm
50
During handling and installation, cable m
0.72
In final installation, cable m
0.5
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,206
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303191
Reka code
1149302
Nominal diameter of complete cable mm
60
Nominal weight of cable kg/km
5576
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
1.8
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
46
During handling and installation, cable cm
72
In final installation, phase conductor cm
32
In final installation, cable cm
50
During handling and installation, cable m
0.72
In final installation, cable m
0.5
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,206
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176303184
Reka code
1149302