AHXAMK-WM 12/20 (24) kV 3-core
Download product group datasheet
Medium-voltage cable for fixed installations outdoors. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.
Standards | HD 620 10 F, SFS 5636 |
---|---|
Conductor | Watertight, circular, stranded aluminium, EN/IEC 60228 class 2 |
Conductor screen | Semiconducting cross-linked polyethylene XLPE |
Insulation | Cross-linked polyethylene XLPE |
Insulation screen | Semiconducting cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | White phase numbering: L1, L2, L3 |
Cable lay up | Three sheathed cores are laid up around a polyethylene insulated galvanized steel messenger |
Inner covering | Semiconducting waterswellable tape against longitudinal water penetration |
Metal screen | Polyethylene laminated aluminium foil, which acts also as a radial water barrier |
Oversheath | PE-plastic PELLD |
Colour of the oversheath | Black |
3x50+62
Electric number
Size
Packaging
Voltage
3x50+62
Nominal diameter of complete cable mm
65
Nominal weight of cable kg/km
2257
Conductor material
Aluminium
Nominal diameter of conductor mm
8
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
19.3
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
38
During handling and installation, cable cm
78
In final installation, phase conductor cm
26
In final installation, cable cm
55
During handling and installation, phase conductor m
0.38
During handling and installation, cable m
0.78
In final installation, phase conductor m
0.26
In final installation, cable m
0.55
Max. pulling force
Pulling-eye kN
7.5
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,641
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022441
Reka code
1187142
3x70+62
Electric number
Size
Packaging
Voltage
3x70+62
Nominal diameter of complete cable mm
69
Nominal weight of cable kg/km
2552
Conductor material
Aluminium
Nominal diameter of conductor mm
9.5
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
20.7
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
41
During handling and installation, cable cm
82
In final installation, phase conductor cm
28
In final installation, cable cm
58
During handling and installation, phase conductor m
0.41
During handling and installation, cable m
0.82
In final installation, phase conductor m
0.28
In final installation, cable m
0.57
Max. pulling force
Pulling-eye kN
10.5
Pulling-stocking kN
3.2
Resistance 20 °C Ω/km
0,443
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022458
Reka code
1187143
3x95+62
Electric number
Size
Packaging
Voltage
3x95+62
Nominal diameter of complete cable mm
72
Nominal weight of cable kg/km
2882
Conductor material
Aluminium
Nominal diameter of conductor mm
11.1
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
22.4
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
44
During handling and installation, cable cm
86
In final installation, phase conductor cm
30
In final installation, cable cm
60
During handling and installation, phase conductor m
0.44
During handling and installation, cable m
0.86
In final installation, phase conductor m
0.3
In final installation, cable m
0.6
Max. pulling force
Pulling-eye kN
14.3
Pulling-stocking kN
4.3
Resistance 20 °C Ω/km
0,320
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022465
Reka code
1187144
3x120+62
Electric number
Size
Packaging
Voltage
3x120+62
Nominal diameter of complete cable mm
75
Nominal weight of cable kg/km
3254
Conductor material
Aluminium
Nominal diameter of conductor mm
12.6
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
23.8
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
45
During handling and installation, cable cm
90
In final installation, phase conductor cm
32
In final installation, cable cm
63
During handling and installation, phase conductor m
0.45
During handling and installation, cable m
0.9
In final installation, phase conductor m
0.32
In final installation, cable m
0.63
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,253
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022472
Reka code
1187145
3x150+62
Electric number
Size
Packaging
Voltage
3x150+62
Nominal diameter of complete cable mm
78
Nominal weight of cable kg/km
3568
Conductor material
Aluminium
Nominal diameter of conductor mm
13.9
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
25.3
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
48
During handling and installation, cable cm
94
In final installation, phase conductor cm
34
In final installation, cable cm
66
During handling and installation, phase conductor m
0.48
During handling and installation, cable m
0.94
In final installation, phase conductor m
0.34
In final installation, cable m
0.66
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
6.8
Resistance 20 °C Ω/km
0,206
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022489
Reka code
1187146
3x185+62
Electric number
Size
Packaging
Voltage
3x185+62
Nominal diameter of complete cable mm
80
Nominal weight of cable kg/km
4100
Conductor material
Aluminium
Nominal diameter of conductor mm
15.6
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
26.8
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
50
During handling and installation, cable cm
96
In final installation, phase conductor cm
35
In final installation, cable cm
67
During handling and installation, phase conductor m
0.5
During handling and installation, cable m
0.96
In final installation, phase conductor m
0.35
In final installation, cable m
0.67
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.3
Resistance 20 °C Ω/km
0,164
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022694
Reka code
1187147
3x240+62
Electric number
Size
Packaging
Voltage
3x240+62
Nominal diameter of complete cable mm
86
Nominal weight of cable kg/km
4815
Conductor material
Aluminium
Nominal diameter of conductor mm
17.8
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
29.2
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
54
During handling and installation, cable cm
103
In final installation, phase conductor cm
38
In final installation, cable cm
72
During handling and installation, phase conductor m
0.54
During handling and installation, cable m
1.03
In final installation, phase conductor m
0.38
In final installation, cable m
0.72
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300107