AHXAMK-WM 12/20 (24) kV 3-core

Download product group datasheet

Medium-voltage cable for fixed installations outdoors. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.

Standards HD 620 10 F, SFS 5636
Conductor Watertight, circular, stranded aluminium, EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) White phase numbering: L1, L2, L3
Cable lay up Three sheathed cores are laid up around a polyethylene insulated galvanized steel messenger
Inner covering Semiconducting waterswellable tape against longitudinal water penetration
Metal screen Polyethylene laminated aluminium foil, which acts also as a radial water barrier
Oversheath PE-plastic PELLD
Colour of the oversheath Black

3x50+62

Electric number Size Packaging Voltage

3x50+62

Nominal diameter of complete cable mm 65
Nominal weight of cable kg/km 2257
Conductor material Aluminium
Nominal diameter of conductor mm 8
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 19.3
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 38
During handling and installation, cable cm 78
In final installation, phase conductor cm 26
In final installation, cable cm 55
During handling and installation, phase conductor m 0.38
During handling and installation, cable m 0.78
In final installation, phase conductor m 0.26
In final installation, cable m 0.55
Max. pulling force
Pulling-eye kN 7.5
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0,641
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022441
Reka code 1187142

3x70+62

Electric number Size Packaging Voltage

3x70+62

Nominal diameter of complete cable mm 69
Nominal weight of cable kg/km 2552
Conductor material Aluminium
Nominal diameter of conductor mm 9.5
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 20.7
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 41
During handling and installation, cable cm 82
In final installation, phase conductor cm 28
In final installation, cable cm 58
During handling and installation, phase conductor m 0.41
During handling and installation, cable m 0.82
In final installation, phase conductor m 0.28
In final installation, cable m 0.57
Max. pulling force
Pulling-eye kN 10.5
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0,443
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022458
Reka code 1187143

3x95+62

Electric number Size Packaging Voltage

3x95+62

Nominal diameter of complete cable mm 72
Nominal weight of cable kg/km 2882
Conductor material Aluminium
Nominal diameter of conductor mm 11.1
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 22.4
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 44
During handling and installation, cable cm 86
In final installation, phase conductor cm 30
In final installation, cable cm 60
During handling and installation, phase conductor m 0.44
During handling and installation, cable m 0.86
In final installation, phase conductor m 0.3
In final installation, cable m 0.6
Max. pulling force
Pulling-eye kN 14.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022465
Reka code 1187144

3x120+62

Electric number Size Packaging Voltage

3x120+62

Nominal diameter of complete cable mm 75
Nominal weight of cable kg/km 3254
Conductor material Aluminium
Nominal diameter of conductor mm 12.6
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 23.8
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 45
During handling and installation, cable cm 90
In final installation, phase conductor cm 32
In final installation, cable cm 63
During handling and installation, phase conductor m 0.45
During handling and installation, cable m 0.9
In final installation, phase conductor m 0.32
In final installation, cable m 0.63
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,253
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022472
Reka code 1187145

3x150+62

Electric number Size Packaging Voltage

3x150+62

Nominal diameter of complete cable mm 78
Nominal weight of cable kg/km 3568
Conductor material Aluminium
Nominal diameter of conductor mm 13.9
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 25.3
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 48
During handling and installation, cable cm 94
In final installation, phase conductor cm 34
In final installation, cable cm 66
During handling and installation, phase conductor m 0.48
During handling and installation, cable m 0.94
In final installation, phase conductor m 0.34
In final installation, cable m 0.66
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0,206
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022489
Reka code 1187146

3x185+62

Electric number Size Packaging Voltage

3x185+62

Nominal diameter of complete cable mm 80
Nominal weight of cable kg/km 4100
Conductor material Aluminium
Nominal diameter of conductor mm 15.6
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 26.8
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 50
During handling and installation, cable cm 96
In final installation, phase conductor cm 35
In final installation, cable cm 67
During handling and installation, phase conductor m 0.5
During handling and installation, cable m 0.96
In final installation, phase conductor m 0.35
In final installation, cable m 0.67
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0,164
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022694
Reka code 1187147

3x240+62

Electric number Size Packaging Voltage

3x240+62

Nominal diameter of complete cable mm 86
Nominal weight of cable kg/km 4815
Conductor material Aluminium
Nominal diameter of conductor mm 17.8
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 29.2
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 54
During handling and installation, cable cm 103
In final installation, phase conductor cm 38
In final installation, cable cm 72
During handling and installation, phase conductor m 0.54
During handling and installation, cable m 1.03
In final installation, phase conductor m 0.38
In final installation, cable m 0.72
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176300107
Reka code 1187148