AHXAMK-WP 19/33 (36) kV 1-core

Download product group datasheet

DryRex Nordic Wind cables are designed especially to meet the requirements of 36 kV wind farms. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.

Standards HD 620 10 F, SFS 5636
Product Environmental Profile (PEP) PEP NXNS-00449-V01.01-EN.pdf
Conductor Watertight, circular, stranded aluminium EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Inner covering Semiconducting waterswellable tape against longitudinal water penetration
Metal screen Polyethylene laminated aluminium foil, which acts also as a radial water barrier
Oversheath PE-plastic PELLD
Colour of the oversheath Black

1x400

Electric number Size Packaging Voltage

1x400

Nominal diameter of complete cable mm 46
Nominal weight of cable kg/km 2193
Conductor material Aluminium
Nominal diameter of conductor mm 22.4
Nominal cross-sectional area of conductor mm2 400
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 38
Number of wires 1
Min. bending radius
During handling and installation, cable cm 70
In final installation, cable cm 49
During handling and installation, cable m 0.7
In final installation, cable m 0.49
Max. pulling force
Pulling-eye kN 12
Pulling-stocking kN 6
Resistance 20 °C Ω/km 0,0778
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306062
Reka code 1181881

1x500

Electric number Size Packaging Voltage

1x500

Nominal diameter of complete cable mm 49
Nominal weight of cable kg/km 2671
Conductor material Aluminium
Nominal diameter of conductor mm 25.7
Nominal cross-sectional area of conductor mm2 500
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 41.3
Number of wires 1
Min. bending radius
During handling and installation, cable cm 75
In final installation, cable cm 53
During handling and installation, cable m 0.75
In final installation, cable m 0.53
Max. pulling force
Pulling-eye kN 15
Pulling-stocking kN 7.5
Resistance 20 °C Ω/km 0,0605
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306079
Reka code 1181882

1x630

Electric number Size Packaging Voltage

1x630

Nominal diameter of complete cable mm 53
Nominal weight of cable kg/km 3266
Conductor material Aluminium
Nominal diameter of conductor mm 29.3
Nominal cross-sectional area of conductor mm2 630
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 45.2
Number of wires 1
Min. bending radius
During handling and installation, cable cm 81
In final installation, cable cm 57
During handling and installation, cable m 0.81
In final installation, cable m 0.57
Max. pulling force
Pulling-eye kN 18.9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0469
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306086
Reka code 1181883

1x800

Electric number Size Packaging Voltage

1x800

Nominal diameter of complete cable mm 57
Nominal weight of cable kg/km 3946
Conductor material Aluminium
Nominal diameter of conductor mm 33.3
Nominal cross-sectional area of conductor mm2 800
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 49.1
Number of wires 1
Min. bending radius
During handling and installation, cable cm 87
In final installation, cable cm 61
During handling and installation, cable m 0.88
In final installation, cable m 0.61
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0367
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306093
Reka code 1181884

1x1000

Electric number Size Packaging Voltage

1x1000

Nominal diameter of complete cable mm 64
Nominal weight of cable kg/km 4722
Conductor material Aluminium
Nominal diameter of conductor mm 37.8
Nominal cross-sectional area of conductor mm2 1000
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 55
Number of wires 1
Min. bending radius
During handling and installation, cable cm 97
In final installation, cable cm 68
During handling and installation, cable m 0.97
In final installation, cable m 0.68
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0291
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306109
Reka code 1181885