AHXAMK-WP 19/33 (36) kV 3-core
Download product group datasheet
DryRex Nordic Wind cables are designed especially to meet the requirements of 36 kV wind farms. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.
Standards | HD 620 10 F, SFS 5636 |
---|---|
Product Environmental Profile (PEP) | PEP NXNS-00437-V01.01-EN.pdf |
Conductor | Watertight, circular, stranded aluminium EN/IEC 60228 class 2 |
Conductor screen | Semiconducting cross-linked polyethylene XLPE |
Insulation | Cross-linked polyethylene XLPE |
Insulation screen | Semiconducting cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | White phase numbering: L1, L2, L3 |
Cable lay up | Three sheathed cores are laid up together |
Inner covering | Semiconducting waterswellable tape against longitudinal water penetration |
Metal screen | Polyethylene laminated aluminium foil, which acts also as a radial water barrier |
Oversheath | PE-plastic PELLD |
Colour of the oversheath | Black |
3x95
Electric number
Size
Packaging
Voltage
3x95
Nominal diameter of complete cable mm
76
Nominal weight of cable kg/km
3332
Conductor material
Aluminium
Nominal diameter of conductor mm
11.1
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
8
Nominal diameter over the insulation without insulation screen mm
26.7
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
53
During handling and installation, cable cm
91
In final installation, phase conductor cm
37
In final installation, cable cm
64
During handling and installation, phase conductor m
0.53
During handling and installation, cable m
0.91
In final installation, phase conductor m
0.37
In final installation, cable m
0.64
Max. pulling force
Pulling-eye kN
8.6
Pulling-stocking kN
4.3
Resistance 20 °C Ω/km
0,320
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176306116
Reka code
1181888
3x120
Electric number
Size
Packaging
Voltage
3x120
Nominal diameter of complete cable mm
79
Nominal weight of cable kg/km
3732
Conductor material
Aluminium
Nominal diameter of conductor mm
12.6
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
8
Nominal diameter over the insulation without insulation screen mm
28.2
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
56
During handling and installation, cable cm
95
In final installation, phase conductor cm
39
In final installation, cable cm
66
During handling and installation, phase conductor m
0.56
During handling and installation, cable m
0.95
In final installation, phase conductor m
0.39
In final installation, cable m
0.67
Max. pulling force
Pulling-eye kN
10.8
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,253
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176306123
Reka code
1181889
3x150
Electric number
Size
Packaging
Voltage
3x150
Nominal diameter of complete cable mm
82
Nominal weight of cable kg/km
4108
Conductor material
Aluminium
Nominal diameter of conductor mm
13.9
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
8
Nominal diameter over the insulation without insulation screen mm
29.5
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
57
During handling and installation, cable cm
99
In final installation, phase conductor cm
40
In final installation, cable cm
69
During handling and installation, phase conductor m
0.57
During handling and installation, cable m
0.99
In final installation, phase conductor m
0.4
In final installation, cable m
0.69
Max. pulling force
Pulling-eye kN
13.5
Pulling-stocking kN
6.8
Resistance 20 °C Ω/km
0,206
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176306260
Reka code
1181890
3x185
Electric number
Size
Packaging
Voltage
3x185
Nominal diameter of complete cable mm
86
Nominal weight of cable kg/km
4625
Conductor material
Aluminium
Nominal diameter of conductor mm
15.6
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
8
Nominal diameter over the insulation without insulation screen mm
31.2
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
60
During handling and installation, cable cm
103
In final installation, phase conductor cm
42
In final installation, cable cm
72
During handling and installation, phase conductor m
0.6
During handling and installation, cable m
1.03
In final installation, phase conductor m
0.42
In final installation, cable m
0.72
Max. pulling force
Pulling-eye kN
16.7
Pulling-stocking kN
8.3
Resistance 20 °C Ω/km
0,164
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176306130
Reka code
1181891
3x240
Electric number
Size
Packaging
Voltage
3x240
Nominal diameter of complete cable mm
92
Nominal weight of cable kg/km
5391
Conductor material
Aluminium
Nominal diameter of conductor mm
17.8
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
8
Nominal diameter over the insulation without insulation screen mm
33.6
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
65
During handling and installation, cable cm
110
In final installation, phase conductor cm
45
In final installation, cable cm
77
During handling and installation, phase conductor m
0.65
During handling and installation, cable m
1.1
In final installation, phase conductor m
0.45
In final installation, cable m
0.77
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176306147
Reka code
1181892
3x300
Electric number
Size
Packaging
Voltage
3x300
Nominal diameter of complete cable mm
96
Nominal weight of cable kg/km
6166
Conductor material
Aluminium
Nominal diameter of conductor mm
19.8
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
8
Nominal diameter over the insulation without insulation screen mm
35.4
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
68
During handling and installation, cable cm
115
In final installation, phase conductor cm
47
In final installation, cable cm
80
During handling and installation, phase conductor m
0.68
During handling and installation, cable m
1.15
In final installation, phase conductor m
0.47
In final installation, cable m
0.81
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176306154
Reka code
1181893