AXCMK-HF C / AXQJ C / IFSI-Al C
Download product group datasheet
Aluminium power cable for fixed installations indoors and outdoors. May be buried directly in soil. Can also be used in medical facilities where higher fire class is required. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Cca-s1,d1,a1.
Standards | SFS 5546, SEK TS 424 14 18-1, HD 604 5 I & D, IEC 60502-1 |
---|---|
Reaction to fire | Cca-s1,d1,a1 |
CPR - DoP | 2018011_DOP.pdf 2019011_DOP.pdf |
Conductor | 25 mm² circular stranded aluminium, EN/IEC 60228 class 2 35-300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2 |
Insulation | Cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | Brown, black, grey Blue, brown, black, grey |
Inner covering | Plastic tape |
Metal screen | Copper wires and copper tape |
Oversheath | UV-protected polyolefin compound |
Colour of the oversheath | Black |
3x35/16
Electric number
Size
Packaging
Voltage
3x35/16
Nominal diameter of complete cable mm
22
Nominal weight of cable kg/km
682
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
17
During handling and installation, cable cm
27
In final installation, phase conductor cm
12
In final installation, cable cm
19
During handling and installation, cable m
0.27
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
1.6
Pulling-stocking kN
1.6
Resistance 20 °C Ω/km
0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300756
Reka code
1149242
Nominal diameter of complete cable mm
22
Nominal weight of cable kg/km
682
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
17
During handling and installation, cable cm
27
In final installation, phase conductor cm
12
In final installation, cable cm
19
During handling and installation, cable m
0.27
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
1.6
Pulling-stocking kN
1.6
Resistance 20 °C Ω/km
0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300749
Reka code
1149242
3x50/16
Electric number
Size
Packaging
Voltage
3x50/16
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
821
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
20
During handling and installation, cable cm
29
In final installation, phase conductor cm
14
In final installation, cable cm
20
During handling and installation, cable m
0.28
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.3
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300770
Reka code
1149243
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
821
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
20
During handling and installation, cable cm
29
In final installation, phase conductor cm
14
In final installation, cable cm
20
During handling and installation, cable m
0.28
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.3
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300763
Reka code
1149243
3x70/21
Electric number
Size
Packaging
Voltage
3x70/21
Nominal diameter of complete cable mm
28
Nominal weight of cable kg/km
1133
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
24
During handling and installation, cable cm
33
In final installation, phase conductor cm
17
In final installation, cable cm
23
During handling and installation, cable m
0.33
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
3.2
Pulling-stocking kN
3.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300794
Reka code
1149244
Nominal diameter of complete cable mm
28
Nominal weight of cable kg/km
1133
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
24
During handling and installation, cable cm
33
In final installation, phase conductor cm
17
In final installation, cable cm
23
During handling and installation, cable m
0.33
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
3.2
Pulling-stocking kN
3.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300787
Reka code
1149244
3x95/29
Electric number
Size
Packaging
Voltage
3x95/29
Nominal diameter of complete cable mm
32
Nominal weight of cable kg/km
1474
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
27
During handling and installation, cable cm
39
In final installation, phase conductor cm
19
In final installation, cable cm
27
During handling and installation, cable m
0.39
In final installation, cable m
0.27
Max. pulling force
Pulling-eye kN
4.3
Pulling-stocking kN
4.3
Resistance 20 °C Ω/km
0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,641
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300800
Reka code
1149245
3x120/41
Electric number
Size
Packaging
Voltage
3x120/41
Nominal diameter of complete cable mm
36
Nominal weight of cable kg/km
1907
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
31
During handling and installation, cable cm
43
In final installation, phase conductor cm
22
In final installation, cable cm
30
During handling and installation, cable m
0.43
In final installation, cable m
0.3
Max. pulling force
Pulling-eye kN
5.4
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300817
Reka code
1149246
3x150/41
Electric number
Size
Packaging
Voltage
3x150/41
Nominal diameter of complete cable mm
40
Nominal weight of cable kg/km
2215
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
35
During handling and installation, cable cm
47
In final installation, phase conductor cm
24
In final installation, cable cm
33
During handling and installation, cable m
0.47
In final installation, cable m
0.33
Max. pulling force
Pulling-eye kN
6.8
Pulling-stocking kN
6.8
Resistance 20 °C Ω/km
0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300824
Reka code
1149247
3x185/57
Electric number
Size
Packaging
Voltage
3x185/57
Nominal diameter of complete cable mm
45
Nominal weight of cable kg/km
2765
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
38
During handling and installation, cable cm
54
In final installation, phase conductor cm
27
In final installation, cable cm
38
During handling and installation, cable m
0.54
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
8.3
Pulling-stocking kN
8.3
Resistance 20 °C Ω/km
0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,320
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300831
Reka code
1149248
3x240/72
Electric number
Size
Packaging
Voltage
3x240/72
Nominal diameter of complete cable mm
48
Nominal weight of cable kg/km
3562
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
43
During handling and installation, cable cm
58
In final installation, phase conductor cm
30
In final installation, cable cm
41
During handling and installation, cable m
0.58
In final installation, cable m
0.41
Max. pulling force
Pulling-eye kN
10.8
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,253
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300848
Reka code
1149249
3x300/88
Electric number
Size
Packaging
Voltage
3x300/88
Nominal diameter of complete cable mm
56
Nominal weight of cable kg/km
4364
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
1.8
Number of wires
3
Min. bending radius
During handling and installation, phase conductor cm
50
During handling and installation, cable cm
67
In final installation, phase conductor cm
35
In final installation, cable cm
47
During handling and installation, cable m
0.67
In final installation, cable m
0.47
Max. pulling force
Pulling-eye kN
13.5
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,206
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300855
Reka code
1149250
4x25/16
Electric number
Size
Packaging
Voltage
4x25/16
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
936
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
9
During handling and installation, cable cm
32
In final installation, phase conductor cm
6
In final installation, cable cm
22
During handling and installation, cable m
0.32
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
1.5
Pulling-stocking kN
1.5
Resistance 20 °C Ω/km
1,20
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300879
Reka code
1149253
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
936
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
9
During handling and installation, cable cm
32
In final installation, phase conductor cm
6
In final installation, cable cm
22
During handling and installation, cable m
0.32
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
1.5
Pulling-stocking kN
1.5
Resistance 20 °C Ω/km
1,20
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300862
Reka code
1149253
4x35/16
Electric number
Size
Packaging
Voltage
4x35/16
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
816
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
16
During handling and installation, cable cm
29
In final installation, phase conductor cm
11
In final installation, cable cm
20
During handling and installation, cable m
0.29
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.1
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300886
Reka code
1149254
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
816
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
16
During handling and installation, cable cm
29
In final installation, phase conductor cm
11
In final installation, cable cm
20
During handling and installation, cable m
0.29
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.1
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300893
Reka code
1149254
4x50/16
Electric number
Size
Packaging
Voltage
4x50/16
Nominal diameter of complete cable mm
28
Nominal weight of cable kg/km
1030
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
19
During handling and installation, cable cm
34
In final installation, phase conductor cm
13
In final installation, cable cm
24
During handling and installation, cable m
0.34
In final installation, cable m
0.24
Max. pulling force
Pulling-eye kN
3
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300916
Reka code
1149255
Nominal diameter of complete cable mm
28
Nominal weight of cable kg/km
1030
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
19
During handling and installation, cable cm
34
In final installation, phase conductor cm
13
In final installation, cable cm
24
During handling and installation, cable m
0.34
In final installation, cable m
0.24
Max. pulling force
Pulling-eye kN
3
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300909
Reka code
1149255
4x70/21
Electric number
Size
Packaging
Voltage
4x70/21
Nominal diameter of complete cable mm
31
Nominal weight of cable kg/km
1409
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
23
During handling and installation, cable cm
38
In final installation, phase conductor cm
16
In final installation, cable cm
26
During handling and installation, cable m
0.38
In final installation, cable m
0.26
Max. pulling force
Pulling-eye kN
4.2
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300930
Reka code
1149256
Nominal diameter of complete cable mm
31
Nominal weight of cable kg/km
1409
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
23
During handling and installation, cable cm
38
In final installation, phase conductor cm
16
In final installation, cable cm
26
During handling and installation, cable m
0.38
In final installation, cable m
0.26
Max. pulling force
Pulling-eye kN
4.2
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300923
Reka code
1149256
4x95/29
Electric number
Size
Packaging
Voltage
4x95/29
Nominal diameter of complete cable mm
35
Nominal weight of cable kg/km
1825
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
26
During handling and installation, cable cm
43
In final installation, phase conductor cm
18
In final installation, cable cm
30
During handling and installation, cable m
0.42
In final installation, cable m
0.3
Max. pulling force
Pulling-eye kN
5.7
Pulling-stocking kN
5.7
Resistance 20 °C Ω/km
0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,641
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300947
Reka code
1149257
4x120/41
Electric number
Size
Packaging
Voltage
4x120/41
Nominal diameter of complete cable mm
41
Nominal weight of cable kg/km
2344
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
29
During handling and installation, cable cm
49
In final installation, phase conductor cm
20
In final installation, cable cm
34
During handling and installation, cable m
0.49
In final installation, cable m
0.34
Max. pulling force
Pulling-eye kN
7.2
Pulling-stocking kN
7.2
Resistance 20 °C Ω/km
0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300954
Reka code
1149258
4x150/41
Electric number
Size
Packaging
Voltage
4x150/41
Nominal diameter of complete cable mm
45
Nominal weight of cable kg/km
2802
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
32
During handling and installation, cable cm
54
In final installation, phase conductor cm
23
In final installation, cable cm
38
During handling and installation, cable m
0.54
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
9
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300961
Reka code
1149259
4x185/57
Electric number
Size
Packaging
Voltage
4x185/57
Nominal diameter of complete cable mm
50
Nominal weight of cable kg/km
3471
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
37
During handling and installation, cable cm
60
In final installation, phase conductor cm
26
In final installation, cable cm
42
During handling and installation, cable m
0.6
In final installation, cable m
0.42
Max. pulling force
Pulling-eye kN
11.1
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,320
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300978
Reka code
1149260
4x240/72
Electric number
Size
Packaging
Voltage
4x240/72
Nominal diameter of complete cable mm
57
Nominal weight of cable kg/km
4514
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
43
During handling and installation, cable cm
68
In final installation, phase conductor cm
30
In final installation, cable cm
48
During handling and installation, cable m
0.68
In final installation, cable m
0.47
Max. pulling force
Pulling-eye kN
14.4
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,253
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300985
Reka code
1149261
4x300/88
Electric number
Size
Packaging
Voltage
4x300/88
Nominal diameter of complete cable mm
60
Nominal weight of cable kg/km
5447
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
1.8
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
46
During handling and installation, cable cm
72
In final installation, phase conductor cm
32
In final installation, cable cm
51
During handling and installation, cable m
0.72
In final installation, cable m
0.51
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,206
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176300992
Reka code
1149262