AXLJ-F TT 18/30 (36) kV 1-core CAS

Download product group datasheet

Medium-voltage cable for fixed installations outdoors. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.

Standards HD 620 10 M, SS 424 14 16
Conductor Watertight, circular, stranded aluminium, EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Inner covering Water swellable tape under and over screen
Metal screen Copper wires and aluminium foil (CAS). Polyethylene laminated aluminium foil acts as a part of the metallic screen and needs to be connected in cable joints and terminations
Radial watertightness Polyethylene laminated aluminium foil bonded to the sheath
Oversheath PE-plastic PELLD
Colour of the oversheath Black

1x150/25 CAS

Electric number Size Packaging Voltage

1x150/25 CAS

Nominal diameter of complete cable mm 38
Nominal weight of cable kg/km 1402
Conductor material Aluminium
Nominal diameter of conductor mm 13.9
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 29.5
Number of wires 1
Nominal size of metal screen mm2 25
Min. bending radius
During handling and installation, cable cm 58
In final installation, cable cm 40
During handling and installation, cable m 0.58
In final installation, cable m 0.4
Max. pulling force
Pulling-eye kN 4.5
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,8
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176217498
Reka code 1186376

1x240/35 CAS

Electric number Size Packaging Voltage

1x240/35 CAS

Nominal diameter of complete cable mm 43
Nominal weight of cable kg/km 1862
Conductor material Aluminium
Nominal diameter of conductor mm 17.8
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 33.4
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable cm 64
In final installation, cable cm 45
During handling and installation, cable m 0.64
In final installation, cable m 0.45
Max. pulling force
Pulling-eye kN 7.2
Pulling-stocking kN 3.6
Resistance 20 °C Ω/km 0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,6
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176217559
Reka code 1186238

1x400/35 CAS

Electric number Size Packaging Voltage

1x400/35 CAS

Nominal diameter of complete cable mm 48
Nominal weight of cable kg/km 2384
Conductor material Aluminium
Nominal diameter of conductor mm 22.4
Nominal cross-sectional area of conductor mm2 400
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 38
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable cm 71
In final installation, cable cm 50
During handling and installation, cable m 0.71
In final installation, cable m 0.5
Max. pulling force
Pulling-eye kN 12
Pulling-stocking kN 6
Resistance 20 °C Ω/km 0,0778
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,6
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176217634
Reka code 1186380

1x500/35 CAS

Electric number Size Packaging Voltage

1x500/35 CAS

Nominal diameter of complete cable mm 51
Nominal weight of cable kg/km 2862
Conductor material Aluminium
Nominal diameter of conductor mm 25.7
Nominal cross-sectional area of conductor mm2 500
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 41.3
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable cm 77
In final installation, cable cm 54
During handling and installation, cable m 0.77
In final installation, cable m 0.54
Max. pulling force
Pulling-eye kN 15
Pulling-stocking kN 7.5
Resistance 20 °C Ω/km 0,0605
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,6
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176217672
Reka code 1186699

1x630/35 CAS

Electric number Size Packaging Voltage

1x630/35 CAS

Nominal diameter of complete cable mm 55
Nominal weight of cable kg/km 3454
Conductor material Aluminium
Nominal diameter of conductor mm 29.3
Nominal cross-sectional area of conductor mm2 630
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 45.1
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable cm 82
In final installation, cable cm 58
During handling and installation, cable m 0.82
In final installation, cable m 0.58
Max. pulling force
Pulling-eye kN 18.9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0469
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,6
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176217696