AXMK
Download product group datasheet
Aluminium power cable for fixed installations indoors and outdoors. May be buried directly in soil. UV-protected oversheath and core insulation. Installations must be in accordance with national regulations and rules of installations. The cable is flame-retardant according to CPR-class Eca.
Standards | SFS 4879, SEK TS 424 14 18-1, HD 603 5 D & O |
---|---|
Reaction to fire | Eca |
CPR - DoP | 2017011_DOP.pdf 2017030_DOP.pdf |
Conductor | 16-25 mm² circular stranded aluminium, EN/IEC 60228 class 2 35-300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2 |
Insulation | UV-protected cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | Black Yellow-green, brown, black, grey Yellow-green, blue, brown, black, grey |
Inner covering | Plastic tape |
Oversheath | UV-protected PVC-compound |
Colour of the oversheath | Black |
4x16 S
Electric number
Size
Packaging
Voltage
4x16 S
Nominal diameter of complete cable mm
19
Nominal weight of cable kg/km
367
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
10
During handling and installation, cable cm
23
In final installation, phase conductor cm
7
In final installation, cable cm
16
During handling and installation, cable m
0.23
In final installation, cable m
0.16
Max. pulling force
Pulling-eye kN
1
Pulling-stocking kN
1
Resistance 20 °C Ω/km
1,91
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262076
Reka code
1116348
Nominal diameter of complete cable mm
19
Nominal weight of cable kg/km
367
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
10
During handling and installation, cable cm
23
In final installation, phase conductor cm
7
In final installation, cable cm
16
During handling and installation, cable m
0.23
In final installation, cable m
0.16
Max. pulling force
Pulling-eye kN
1
Pulling-stocking kN
1
Resistance 20 °C Ω/km
1,91
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262670
Reka code
1116348
4x25 S
Electric number
Size
Packaging
Voltage
4x25 S
Nominal diameter of complete cable mm
22
Nominal weight of cable kg/km
517
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
13
During handling and installation, cable cm
27
In final installation, phase conductor cm
8
In final installation, cable cm
19
During handling and installation, cable m
0.27
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
1.5
Pulling-stocking kN
1.5
Resistance 20 °C Ω/km
1,20
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262083
Reka code
1701199
Nominal diameter of complete cable mm
22
Nominal weight of cable kg/km
517
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
13
During handling and installation, cable cm
27
In final installation, phase conductor cm
8
In final installation, cable cm
19
During handling and installation, cable m
0.27
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
1.5
Pulling-stocking kN
1.5
Resistance 20 °C Ω/km
1,20
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262731
Reka code
1701199
4x35 S
Electric number
Size
Packaging
Voltage
4x35 S
Nominal diameter of complete cable mm
22
Nominal weight of cable kg/km
635
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
16
During handling and installation, cable cm
27
In final installation, phase conductor cm
11
In final installation, cable cm
19
During handling and installation, cable m
0.27
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
2.1
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262687
Reka code
1116332
Nominal diameter of complete cable mm
22
Nominal weight of cable kg/km
635
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
16
During handling and installation, cable cm
27
In final installation, phase conductor cm
11
In final installation, cable cm
19
During handling and installation, cable m
0.27
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
2.1
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262090
Reka code
1116332
4x50 S
Electric number
Size
Packaging
Voltage
4x50 S
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
844
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
19
During handling and installation, cable cm
31
In final installation, phase conductor cm
13
In final installation, cable cm
22
During handling and installation, cable m
0.31
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
3
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,641
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262106
Reka code
1116333
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
844
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
19
During handling and installation, cable cm
31
In final installation, phase conductor cm
13
In final installation, cable cm
22
During handling and installation, cable m
0.31
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
3
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,641
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262694
Reka code
1116333
4x70 S
Electric number
Size
Packaging
Voltage
4x70 S
Nominal diameter of complete cable mm
29
Nominal weight of cable kg/km
1148
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
23
During handling and installation, cable cm
35
In final installation, phase conductor cm
16
In final installation, cable cm
25
During handling and installation, cable m
0.35
In final installation, cable m
0.25
Max. pulling force
Pulling-eye kN
4.2
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262113
Reka code
1116334
Nominal diameter of complete cable mm
29
Nominal weight of cable kg/km
1148
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
23
During handling and installation, cable cm
35
In final installation, phase conductor cm
16
In final installation, cable cm
25
During handling and installation, cable m
0.35
In final installation, cable m
0.25
Max. pulling force
Pulling-eye kN
4.2
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262700
Reka code
1116334
4x95 S
Electric number
Size
Packaging
Voltage
4x95 S
Nominal diameter of complete cable mm
33
Nominal weight of cable kg/km
1538
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
26
During handling and installation, cable cm
39
In final installation, phase conductor cm
18
In final installation, cable cm
28
During handling and installation, cable m
0.39
In final installation, cable m
0.28
Max. pulling force
Pulling-eye kN
5.7
Pulling-stocking kN
5.7
Resistance 20 °C Ω/km
0,320
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262120
Reka code
1116335
Nominal diameter of complete cable mm
33
Nominal weight of cable kg/km
1538
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
26
During handling and installation, cable cm
39
In final installation, phase conductor cm
18
In final installation, cable cm
28
During handling and installation, cable m
0.39
In final installation, cable m
0.28
Max. pulling force
Pulling-eye kN
5.7
Pulling-stocking kN
5.7
Resistance 20 °C Ω/km
0,320
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262717
Reka code
1116335
4x120 S
Electric number
Size
Packaging
Voltage
4x120 S
Nominal diameter of complete cable mm
38
Nominal weight of cable kg/km
1878
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
29
During handling and installation, cable cm
45
In final installation, phase conductor cm
20
In final installation, cable cm
32
During handling and installation, cable m
0.45
In final installation, cable m
0.32
Max. pulling force
Pulling-eye kN
7.2
Pulling-stocking kN
7.2
Resistance 20 °C Ω/km
0,253
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262137
Reka code
1116336
Nominal diameter of complete cable mm
38
Nominal weight of cable kg/km
1878
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
29
During handling and installation, cable cm
45
In final installation, phase conductor cm
20
In final installation, cable cm
32
During handling and installation, cable m
0.45
In final installation, cable m
0.32
Max. pulling force
Pulling-eye kN
7.2
Pulling-stocking kN
7.2
Resistance 20 °C Ω/km
0,253
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262724
Reka code
1116336
4x150 S
Electric number
Size
Packaging
Voltage
4x150 S
Nominal diameter of complete cable mm
42
Nominal weight of cable kg/km
2297
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
32
During handling and installation, cable cm
50
In final installation, phase conductor cm
23
In final installation, cable cm
35
During handling and installation, cable m
0.5
In final installation, cable m
0.35
Max. pulling force
Pulling-eye kN
9
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,206
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262144
Reka code
1116337
4x185 S
Electric number
Size
Packaging
Voltage
4x185 S
Nominal diameter of complete cable mm
46
Nominal weight of cable kg/km
2798
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
37
During handling and installation, cable cm
55
In final installation, phase conductor cm
26
In final installation, cable cm
39
During handling and installation, cable m
0.55
In final installation, cable m
0.39
Max. pulling force
Pulling-eye kN
11.1
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,164
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262151
Reka code
1116358
4x240 S
Electric number
Size
Packaging
Voltage
4x240 S
Nominal diameter of complete cable mm
53
Nominal weight of cable kg/km
3679
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
43
During handling and installation, cable cm
63
In final installation, phase conductor cm
30
In final installation, cable cm
44
During handling and installation, cable m
0.63
In final installation, cable m
0.44
Max. pulling force
Pulling-eye kN
14.4
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262168
Reka code
1116359
4x300 S
Electric number
Size
Packaging
Voltage
4x300 S
Nominal diameter of complete cable mm
57
Nominal weight of cable kg/km
4439
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
1.8
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
46
During handling and installation, cable cm
68
In final installation, phase conductor cm
32
In final installation, cable cm
48
During handling and installation, cable m
0.68
In final installation, cable m
0.48
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-40
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006262175
Reka code
1116360