EMCMK-HF C / FXQJ-EMC C / IFSI-EMC-Cu C

Download product group datasheet

Copper power cable for fixed installations indoors and outdoors. May be buried directly in soil. Can also be used in medical facilities where higher fire class is required. EMC shielded cable gives an excellent protection against electromagnetic disturbancies. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Cca-s1,d1,a1.

Standards SFS 5546, SEK TS 424 14 18-1, HD 604 5 I & D, IEC 60502-1
Reaction to fire Cca-s1,d1,a1
CPR - DoP 2019003_DOP.pdf
Conductor Sector shaped, stranded aluminium, EN/IEC 60228 class 2
Insulation Cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Brown, black, grey
Blue, brown, black, grey
Inner covering Plastic tape
Metal screen EMC-copper foil and copper wires
Oversheath UV-protected polyolefin compound
Colour of the oversheath Black

3x35/16

Electric number Size Packaging Voltage

3x35/16

Nominal diameter of complete cable mm 23
Nominal weight of cable kg/km 1378
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 3
Min. bending radius
During handling and installation, cable cm 28
In final installation, cable cm 19
During handling and installation, cable m 0.28
In final installation, cable m 0.19
Max. pulling force
Pulling-eye kN 5.3
Pulling-stocking kN 1.6
Resistance 20 °C Ω/km 0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303221
Reka code 1146777
Nominal diameter of complete cable mm 23
Nominal weight of cable kg/km 1378
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 3
Min. bending radius
During handling and installation, cable cm 28
In final installation, cable cm 19
During handling and installation, cable m 0.28
In final installation, cable m 0.19
Max. pulling force
Pulling-eye kN 5.3
Pulling-stocking kN 1.6
Resistance 20 °C Ω/km 0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303214
Reka code 1146777

3x50/25

Electric number Size Packaging Voltage

3x50/25

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 1877
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 3
Min. bending radius
During handling and installation, cable cm 32
In final installation, cable cm 22
During handling and installation, cable m 0.32
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 7.5
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303252
Reka code 1146778
Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 1877
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 3
Min. bending radius
During handling and installation, cable cm 32
In final installation, cable cm 22
During handling and installation, cable m 0.32
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 7.5
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303245
Reka code 1146778

3x70/35

Electric number Size Packaging Voltage

3x70/35

Nominal diameter of complete cable mm 30
Nominal weight of cable kg/km 2584
Conductor material Copper
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 3
Min. bending radius
During handling and installation, cable cm 36
In final installation, cable cm 26
During handling and installation, cable m 0.36
In final installation, cable m 0.26
Max. pulling force
Pulling-eye kN 10.5
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303276
Reka code 1146779
Nominal diameter of complete cable mm 30
Nominal weight of cable kg/km 2584
Conductor material Copper
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 3
Min. bending radius
During handling and installation, cable cm 36
In final installation, cable cm 26
During handling and installation, cable m 0.36
In final installation, cable m 0.26
Max. pulling force
Pulling-eye kN 10.5
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303283
Reka code 1146779

3x95/50

Electric number Size Packaging Voltage

3x95/50

Nominal diameter of complete cable mm 34
Nominal weight of cable kg/km 3473
Conductor material Copper
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 3
Min. bending radius
During handling and installation, cable cm 40
In final installation, cable cm 28
During handling and installation, cable m 0.4
In final installation, cable m 0.28
Max. pulling force
Pulling-eye kN 14.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303313
Reka code 1146780
Nominal diameter of complete cable mm 34
Nominal weight of cable kg/km 3473
Conductor material Copper
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 3
Min. bending radius
During handling and installation, cable cm 40
In final installation, cable cm 28
During handling and installation, cable m 0.4
In final installation, cable m 0.28
Max. pulling force
Pulling-eye kN 14.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303306
Reka code 1146780

3x120/70

Electric number Size Packaging Voltage

3x120/70

Nominal diameter of complete cable mm 37
Nominal weight of cable kg/km 4342
Conductor material Copper
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 3
Min. bending radius
During handling and installation, cable cm 44
In final installation, cable cm 31
During handling and installation, cable m 0.44
In final installation, cable m 0.31
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303344
Reka code 1146781
Nominal diameter of complete cable mm 37
Nominal weight of cable kg/km 4342
Conductor material Copper
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 3
Min. bending radius
During handling and installation, cable cm 44
In final installation, cable cm 31
During handling and installation, cable m 0.44
In final installation, cable m 0.31
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303337
Reka code 1146781

3x150/70

Electric number Size Packaging Voltage

3x150/70

Nominal diameter of complete cable mm 40
Nominal weight of cable kg/km 5196
Conductor material Copper
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 3
Min. bending radius
During handling and installation, cable cm 48
In final installation, cable cm 34
During handling and installation, cable m 0.48
In final installation, cable m 0.34
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303375
Reka code 1146782
Nominal diameter of complete cable mm 40
Nominal weight of cable kg/km 5196
Conductor material Copper
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 3
Min. bending radius
During handling and installation, cable cm 48
In final installation, cable cm 34
During handling and installation, cable m 0.48
In final installation, cable m 0.34
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303368
Reka code 1146782

3x185/95

Electric number Size Packaging Voltage

3x185/95

Nominal diameter of complete cable mm 45
Nominal weight of cable kg/km 6650
Conductor material Copper
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 3
Min. bending radius
During handling and installation, cable cm 54
In final installation, cable cm 38
During handling and installation, cable m 0.54
In final installation, cable m 0.38
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,193
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303405
Reka code 1146783
Nominal diameter of complete cable mm 45
Nominal weight of cable kg/km 6650
Conductor material Copper
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 3
Min. bending radius
During handling and installation, cable cm 54
In final installation, cable cm 38
During handling and installation, cable m 0.54
In final installation, cable m 0.38
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,193
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303399
Reka code 1146783

3x240/120

Electric number Size Packaging Voltage

3x240/120

Nominal diameter of complete cable mm 51
Nominal weight of cable kg/km 8645
Conductor material Copper
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 61
In final installation, cable cm 43
During handling and installation, cable m 0.61
In final installation, cable m 0.43
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0754
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,153
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303429
Reka code 1146784

3x300/150

Electric number Size Packaging Voltage

3x300/150

Nominal diameter of complete cable mm 54
Nominal weight of cable kg/km 10683
Conductor material Copper
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 3
Min. bending radius
During handling and installation, cable cm 65
In final installation, cable cm 45
During handling and installation, cable m 0.65
In final installation, cable m 0.45
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0601
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,124
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303450
Reka code 1146785

4x35/16

Electric number Size Packaging Voltage

4x35/16

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 1746
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, cable cm 31
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 7
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303481
Reka code 1146794
Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 1746
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, cable cm 31
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 7
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303498
Reka code 1146794

4x50/25

Electric number Size Packaging Voltage

4x50/25

Nominal diameter of complete cable mm 30
Nominal weight of cable kg/km 2372
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 4
Min. bending radius
During handling and installation, cable cm 35
In final installation, cable cm 25
During handling and installation, cable m 0.35
In final installation, cable m 0.25
Max. pulling force
Pulling-eye kN 10
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303528
Reka code 1146795
Nominal diameter of complete cable mm 30
Nominal weight of cable kg/km 2372
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 4
Min. bending radius
During handling and installation, cable cm 35
In final installation, cable cm 25
During handling and installation, cable m 0.35
In final installation, cable m 0.25
Max. pulling force
Pulling-eye kN 10
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303511
Reka code 1146795

4x70/35

Electric number Size Packaging Voltage

4x70/35

Nominal diameter of complete cable mm 34
Nominal weight of cable kg/km 3258
Conductor material Copper
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, cable cm 41
In final installation, cable cm 29
During handling and installation, cable m 0.41
In final installation, cable m 0.29
Max. pulling force
Pulling-eye kN 14
Pulling-stocking kN 4.2
Resistance 20 °C Ω/km 0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303542
Reka code 1146796
Nominal diameter of complete cable mm 34
Nominal weight of cable kg/km 3258
Conductor material Copper
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, cable cm 41
In final installation, cable cm 29
During handling and installation, cable m 0.41
In final installation, cable m 0.29
Max. pulling force
Pulling-eye kN 14
Pulling-stocking kN 4.2
Resistance 20 °C Ω/km 0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303559
Reka code 1146796

4x95/50

Electric number Size Packaging Voltage

4x95/50

Nominal diameter of complete cable mm 38
Nominal weight of cable kg/km 4405
Conductor material Copper
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, cable cm 45
In final installation, cable cm 32
During handling and installation, cable m 0.45
In final installation, cable m 0.32
Max. pulling force
Pulling-eye kN 19
Pulling-stocking kN 5.7
Resistance 20 °C Ω/km 0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303580
Reka code 1146797
Nominal diameter of complete cable mm 38
Nominal weight of cable kg/km 4405
Conductor material Copper
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, cable cm 45
In final installation, cable cm 32
During handling and installation, cable m 0.45
In final installation, cable m 0.32
Max. pulling force
Pulling-eye kN 19
Pulling-stocking kN 5.7
Resistance 20 °C Ω/km 0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303573
Reka code 1146797

4x120/70

Electric number Size Packaging Voltage

4x120/70

Nominal diameter of complete cable mm 42
Nominal weight of cable kg/km 5558
Conductor material Copper
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, cable cm 50
In final installation, cable cm 35
During handling and installation, cable m 0.5
In final installation, cable m 0.35
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 7.2
Resistance 20 °C Ω/km 0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303610
Reka code 1146798
Nominal diameter of complete cable mm 42
Nominal weight of cable kg/km 5558
Conductor material Copper
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, cable cm 50
In final installation, cable cm 35
During handling and installation, cable m 0.5
In final installation, cable m 0.35
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 7.2
Resistance 20 °C Ω/km 0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303603
Reka code 1146798

4x150/70

Electric number Size Packaging Voltage

4x150/70

Nominal diameter of complete cable mm 45
Nominal weight of cable kg/km 6699
Conductor material Copper
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, cable cm 55
In final installation, cable cm 38
During handling and installation, cable m 0.55
In final installation, cable m 0.38
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303641
Reka code 1146799
Nominal diameter of complete cable mm 45
Nominal weight of cable kg/km 6699
Conductor material Copper
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, cable cm 55
In final installation, cable cm 38
During handling and installation, cable m 0.55
In final installation, cable m 0.38
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303634
Reka code 1146799

4x185/95

Electric number Size Packaging Voltage

4x185/95

Nominal diameter of complete cable mm 51
Nominal weight of cable kg/km 8523
Conductor material Copper
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 4
Min. bending radius
During handling and installation, cable cm 61
In final installation, cable cm 43
During handling and installation, cable m 0.61
In final installation, cable m 0.43
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,193
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303672
Reka code 1146800
Nominal diameter of complete cable mm 51
Nominal weight of cable kg/km 8523
Conductor material Copper
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 4
Min. bending radius
During handling and installation, cable cm 61
In final installation, cable cm 43
During handling and installation, cable m 0.61
In final installation, cable m 0.43
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,193
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303665
Reka code 1146800

4x240/120

Electric number Size Packaging Voltage

4x240/120

Nominal diameter of complete cable mm 56
Nominal weight of cable kg/km 11033
Conductor material Copper
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 68
In final installation, cable cm 47
During handling and installation, cable m 0.68
In final installation, cable m 0.47
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0754
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,153
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303696
Reka code 1146801

4x300/150

Electric number Size Packaging Voltage

4x300/150

Nominal diameter of complete cable mm 61
Nominal weight of cable kg/km 13688
Conductor material Copper
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 4
Min. bending radius
During handling and installation, cable cm 73
In final installation, cable cm 51
During handling and installation, cable m 0.73
In final installation, cable m 0.51
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0601
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,124
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176303726
Reka code 1146802