EMCMK-HF / EXQJ-EMC / FXQJ-EMC / IFSI-EMC-Cu
Download product group datasheet
Copper power cable for fixed installations indoors and outdoors. May be buried directly in soil. EMC shielded cable gives an excellent protection against electromagnetic disturbancies. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Dca-s2,d2,a2.
Standards | SFS 5546, SEK TS 424 14 18-1, HD 604 5 I & D, IEC 60502-1 |
---|---|
Reaction to fire | Dca-s2,d2,a2 |
CPR - DoP | 2024008_DOP.pdf 2021007_DOP.pdf |
Conductor | 1,5-6 mm² circular solid copper, EN/IEC 60228 class 1 10-25 mm² circular stranded copper, EN/IEC 60228 class 2 35-300 mm² sector shaped stranded copper, EN/IEC 60228 class 2 |
Insulation | Cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | Brown, black, grey Blue, brown, black, grey |
Inner covering | Plastic tape |
Metal screen | EMC-copper foil and copper wires |
Oversheath | UV-protected polyolefin compound |
Colour of the oversheath | Black |
2x1,5/1,5
Electric number
Size
Packaging
Voltage
2x1,5/1,5
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
199
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
14
In final installation, cable cm
10
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.2
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176008690
Reka code
1146739
2x2,5/2,5
Electric number
Size
Packaging
Voltage
2x2,5/2,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
255
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176008713
Reka code
1146740
2x4/4
Electric number
Size
Packaging
Voltage
2x4/4
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
326
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.4
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
4,61
Maximum d.c. resistance at 20 °C, metal screen Ω/km
4,61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176008720
Reka code
1146741
2x6/6
Electric number
Size
Packaging
Voltage
2x6/6
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
407
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
18
In final installation, cable cm
13
During handling and installation, cable m
0.18
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.6
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176008737
Reka code
1146743
2x10/10
Electric number
Size
Packaging
Voltage
2x10/10
Nominal diameter of complete cable mm
18
Nominal weight of cable kg/km
595
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
21
In final installation, cable cm
15
During handling and installation, cable m
0.21
In final installation, cable m
0.15
Max. pulling force
Pulling-eye kN
1
Pulling-stocking kN
0.3
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176008744
Reka code
1146744
2x16/16
Electric number
Size
Packaging
Voltage
2x16/16
Nominal diameter of complete cable mm
20
Nominal weight of cable kg/km
831
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
24
In final installation, cable cm
17
During handling and installation, cable m
0.24
In final installation, cable m
0.17
Max. pulling force
Pulling-eye kN
1.6
Pulling-stocking kN
0.5
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176008751
Reka code
1146745
3x1,5/1,5
Electric number
Size
Packaging
Voltage
3x1,5/1,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
229
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.2
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023721
Reka code
1146690
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
229
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.2
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023738
Reka code
1146690
3x2,5/2,5
Electric number
Size
Packaging
Voltage
3x2,5/2,5
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
285
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.4
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023752
Reka code
1146691
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
285
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.4
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023745
Reka code
1146691
3x4/4
Electric number
Size
Packaging
Voltage
3x4/4
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
365
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
18
In final installation, cable cm
12
During handling and installation, cable m
0.18
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.6
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
4,61
Maximum d.c. resistance at 20 °C, metal screen Ω/km
4,61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176114742
Reka code
1146692
3x6/6
Electric number
Size
Packaging
Voltage
3x6/6
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
463
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
18
In final installation, cable cm
13
During handling and installation, cable m
0.18
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.9
Pulling-stocking kN
0.3
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023905
Reka code
1146693
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
463
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
18
In final installation, cable cm
13
During handling and installation, cable m
0.18
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.9
Pulling-stocking kN
0.3
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023875
Reka code
1146693
3x10/10
Electric number
Size
Packaging
Voltage
3x10/10
Nominal diameter of complete cable mm
19
Nominal weight of cable kg/km
693
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
23
In final installation, cable cm
16
During handling and installation, cable m
0.23
In final installation, cable m
0.16
Max. pulling force
Pulling-eye kN
1.5
Pulling-stocking kN
0.5
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023912
Reka code
1146694
Nominal diameter of complete cable mm
19
Nominal weight of cable kg/km
693
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
23
In final installation, cable cm
16
During handling and installation, cable m
0.23
In final installation, cable m
0.16
Max. pulling force
Pulling-eye kN
1.5
Pulling-stocking kN
0.5
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023929
Reka code
1146694
3x16/16
Electric number
Size
Packaging
Voltage
3x16/16
Nominal diameter of complete cable mm
21
Nominal weight of cable kg/km
972
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
26
In final installation, cable cm
18
During handling and installation, cable m
0.26
In final installation, cable m
0.18
Max. pulling force
Pulling-eye kN
2.4
Pulling-stocking kN
0.7
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023936
Reka code
1146695
Nominal diameter of complete cable mm
21
Nominal weight of cable kg/km
972
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
26
In final installation, cable cm
18
During handling and installation, cable m
0.26
In final installation, cable m
0.18
Max. pulling force
Pulling-eye kN
2.4
Pulling-stocking kN
0.7
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023943
Reka code
1146695
3x25/16
Electric number
Size
Packaging
Voltage
3x25/16
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1395
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, cable cm
31
In final installation, cable cm
22
During handling and installation, cable m
0.31
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
3.8
Pulling-stocking kN
1.1
Resistance 20 °C Ω/km
0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023950
Reka code
1146696
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1395
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, cable cm
31
In final installation, cable cm
22
During handling and installation, cable m
0.31
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
3.8
Pulling-stocking kN
1.1
Resistance 20 °C Ω/km
0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023967
Reka code
1146696
3x35/16
Electric number
Size
Packaging
Voltage
3x35/16
Nominal diameter of complete cable mm
23
Nominal weight of cable kg/km
1374
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, cable cm
28
In final installation, cable cm
19
During handling and installation, cable m
0.28
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
5.3
Pulling-stocking kN
1.6
Resistance 20 °C Ω/km
0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115695
Reka code
1256647
Nominal diameter of complete cable mm
23
Nominal weight of cable kg/km
1374
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, cable cm
28
In final installation, cable cm
19
During handling and installation, cable m
0.28
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
5.3
Pulling-stocking kN
1.6
Resistance 20 °C Ω/km
0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115688
Reka code
1256647
3x50/25
Electric number
Size
Packaging
Voltage
3x50/25
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1871
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
3
Min. bending radius
During handling and installation, cable cm
32
In final installation, cable cm
22
During handling and installation, cable m
0.32
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
7.5
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115701
Reka code
1256648
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1871
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
3
Min. bending radius
During handling and installation, cable cm
32
In final installation, cable cm
22
During handling and installation, cable m
0.32
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
7.5
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115718
Reka code
1256648
3x70/35
Electric number
Size
Packaging
Voltage
3x70/35
Nominal diameter of complete cable mm
30
Nominal weight of cable kg/km
2580
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, cable cm
36
In final installation, cable cm
25
During handling and installation, cable m
0.36
In final installation, cable m
0.26
Max. pulling force
Pulling-eye kN
10.5
Pulling-stocking kN
3.2
Resistance 20 °C Ω/km
0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115732
Reka code
1256649
Nominal diameter of complete cable mm
30
Nominal weight of cable kg/km
2580
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, cable cm
36
In final installation, cable cm
25
During handling and installation, cable m
0.36
In final installation, cable m
0.26
Max. pulling force
Pulling-eye kN
10.5
Pulling-stocking kN
3.2
Resistance 20 °C Ω/km
0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115725
Reka code
1256649
3x95/50
Electric number
Size
Packaging
Voltage
3x95/50
Nominal diameter of complete cable mm
34
Nominal weight of cable kg/km
3468
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, cable cm
40
In final installation, cable cm
28
During handling and installation, cable m
0.4
In final installation, cable m
0.28
Max. pulling force
Pulling-eye kN
14.3
Pulling-stocking kN
4.3
Resistance 20 °C Ω/km
0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,387
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115749
Reka code
1256650
Nominal diameter of complete cable mm
34
Nominal weight of cable kg/km
3468
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
3
Min. bending radius
During handling and installation, cable cm
40
In final installation, cable cm
28
During handling and installation, cable m
0.4
In final installation, cable m
0.28
Max. pulling force
Pulling-eye kN
14.3
Pulling-stocking kN
4.3
Resistance 20 °C Ω/km
0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,387
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115756
Reka code
1256650
3x120/70
Electric number
Size
Packaging
Voltage
3x120/70
Nominal diameter of complete cable mm
37
Nominal weight of cable kg/km
4399
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
3
Min. bending radius
During handling and installation, cable cm
44
In final installation, cable cm
31
During handling and installation, cable m
0.44
In final installation, cable m
0.31
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115763
Reka code
1256651
Nominal diameter of complete cable mm
37
Nominal weight of cable kg/km
4399
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
3
Min. bending radius
During handling and installation, cable cm
44
In final installation, cable cm
31
During handling and installation, cable m
0.44
In final installation, cable m
0.31
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115770
Reka code
1256651
3x150/70
Electric number
Size
Packaging
Voltage
3x150/70
Nominal diameter of complete cable mm
40
Nominal weight of cable kg/km
5266
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
3
Min. bending radius
During handling and installation, cable cm
48
In final installation, cable cm
34
During handling and installation, cable m
0.48
In final installation, cable m
0.34
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
6.8
Resistance 20 °C Ω/km
0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115787
Reka code
1256652
3x185/95
Electric number
Size
Packaging
Voltage
3x185/95
Nominal diameter of complete cable mm
45
Nominal weight of cable kg/km
6646
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
3
Min. bending radius
During handling and installation, cable cm
54
In final installation, cable cm
38
During handling and installation, cable m
0.54
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.3
Resistance 20 °C Ω/km
0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,193
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115800
Reka code
1256653
3x240/120
Electric number
Size
Packaging
Voltage
3x240/120
Nominal diameter of complete cable mm
51
Nominal weight of cable kg/km
8640
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
61
In final installation, cable cm
43
During handling and installation, cable m
0.61
In final installation, cable m
0.43
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,0754
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,153
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115824
Reka code
1256654
4x1,5/1,5
Electric number
Size
Packaging
Voltage
4x1,5/1,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
242
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029143
Reka code
1146710
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
242
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029136
Reka code
1146710
4x2,5/2,5
Electric number
Size
Packaging
Voltage
4x2,5/2,5
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
314
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.5
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029150
Reka code
1146711
4x4/4
Electric number
Size
Packaging
Voltage
4x4/4
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
381
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.8
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
4,61
Maximum d.c. resistance at 20 °C, metal screen Ω/km
4,61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176115145
Reka code
1146712
4x6/6
Electric number
Size
Packaging
Voltage
4x6/6
Nominal diameter of complete cable mm
17
Nominal weight of cable kg/km
545
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
20
In final installation, cable cm
14
During handling and installation, cable m
0.2
In final installation, cable m
0.14
Max. pulling force
Pulling-eye kN
1.2
Pulling-stocking kN
0.4
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029181
Reka code
1146713
Nominal diameter of complete cable mm
17
Nominal weight of cable kg/km
545
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
20
In final installation, cable cm
14
During handling and installation, cable m
0.2
In final installation, cable m
0.14
Max. pulling force
Pulling-eye kN
1.2
Pulling-stocking kN
0.4
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029174
Reka code
1146713
4x10/10
Electric number
Size
Packaging
Voltage
4x10/10
Nominal diameter of complete cable mm
20
Nominal weight of cable kg/km
837
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
24
In final installation, cable cm
17
During handling and installation, cable m
0.24
In final installation, cable m
0.17
Max. pulling force
Pulling-eye kN
2
Pulling-stocking kN
0.6
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029198
Reka code
1146714
Nominal diameter of complete cable mm
20
Nominal weight of cable kg/km
837
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
24
In final installation, cable cm
17
During handling and installation, cable m
0.24
In final installation, cable m
0.17
Max. pulling force
Pulling-eye kN
2
Pulling-stocking kN
0.6
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029204
Reka code
1146714
4x16/16
Electric number
Size
Packaging
Voltage
4x16/16
Nominal diameter of complete cable mm
23
Nominal weight of cable kg/km
1153
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
28
In final installation, cable cm
19
During handling and installation, cable m
0.28
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
3.2
Pulling-stocking kN
1
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029433
Reka code
1146715
Nominal diameter of complete cable mm
23
Nominal weight of cable kg/km
1153
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
28
In final installation, cable cm
19
During handling and installation, cable m
0.28
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
3.2
Pulling-stocking kN
1
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029211
Reka code
1146715
4x25/16
Electric number
Size
Packaging
Voltage
4x25/16
Nominal diameter of complete cable mm
28
Nominal weight of cable kg/km
1683
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, cable cm
34
In final installation, cable cm
23
During handling and installation, cable m
0.34
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
5
Pulling-stocking kN
1.5
Resistance 20 °C Ω/km
0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029457
Reka code
1146716
Nominal diameter of complete cable mm
28
Nominal weight of cable kg/km
1683
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, cable cm
34
In final installation, cable cm
23
During handling and installation, cable m
0.34
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
5
Pulling-stocking kN
1.5
Resistance 20 °C Ω/km
0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029440
Reka code
1146716
4x35/16
Electric number
Size
Packaging
Voltage
4x35/16
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1740
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, cable cm
31
In final installation, cable cm
22
During handling and installation, cable m
0.31
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
7
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116067
Reka code
1256664
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1740
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, cable cm
31
In final installation, cable cm
22
During handling and installation, cable m
0.31
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
7
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116050
Reka code
1256664
4x50/25
Electric number
Size
Packaging
Voltage
4x50/25
Nominal diameter of complete cable mm
30
Nominal weight of cable kg/km
2377
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, cable cm
35
In final installation, cable cm
25
During handling and installation, cable m
0.35
In final installation, cable m
0.25
Max. pulling force
Pulling-eye kN
10
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116081
Reka code
1256665
Nominal diameter of complete cable mm
30
Nominal weight of cable kg/km
2377
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, cable cm
35
In final installation, cable cm
25
During handling and installation, cable m
0.35
In final installation, cable m
0.25
Max. pulling force
Pulling-eye kN
10
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116074
Reka code
1256665
4x70/35
Electric number
Size
Packaging
Voltage
4x70/35
Nominal diameter of complete cable mm
34
Nominal weight of cable kg/km
3278
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, cable cm
41
In final installation, cable cm
29
During handling and installation, cable m
0.41
In final installation, cable m
0.29
Max. pulling force
Pulling-eye kN
14
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116098
Reka code
1256666
Nominal diameter of complete cable mm
34
Nominal weight of cable kg/km
3278
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, cable cm
41
In final installation, cable cm
29
During handling and installation, cable m
0.41
In final installation, cable m
0.29
Max. pulling force
Pulling-eye kN
14
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116104
Reka code
1256666
4x95/50
Electric number
Size
Packaging
Voltage
4x95/50
Nominal diameter of complete cable mm
38
Nominal weight of cable kg/km
4408
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, cable cm
45
In final installation, cable cm
31
During handling and installation, cable m
0.45
In final installation, cable m
0.31
Max. pulling force
Pulling-eye kN
19
Pulling-stocking kN
5.7
Resistance 20 °C Ω/km
0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,387
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116111
Reka code
1256667
Nominal diameter of complete cable mm
38
Nominal weight of cable kg/km
4408
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, cable cm
45
In final installation, cable cm
31
During handling and installation, cable m
0.45
In final installation, cable m
0.31
Max. pulling force
Pulling-eye kN
19
Pulling-stocking kN
5.7
Resistance 20 °C Ω/km
0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,387
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116128
Reka code
1256667
4x120/70
Electric number
Size
Packaging
Voltage
4x120/70
Nominal diameter of complete cable mm
42
Nominal weight of cable kg/km
5584
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
4
Min. bending radius
During handling and installation, cable cm
50
In final installation, cable cm
35
During handling and installation, cable m
0.5
In final installation, cable m
0.35
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
7.2
Resistance 20 °C Ω/km
0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116135
Reka code
1256668
Nominal diameter of complete cable mm
42
Nominal weight of cable kg/km
5584
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
4
Min. bending radius
During handling and installation, cable cm
50
In final installation, cable cm
35
During handling and installation, cable m
0.5
In final installation, cable m
0.35
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
7.2
Resistance 20 °C Ω/km
0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116142
Reka code
1256668
4x150/70
Electric number
Size
Packaging
Voltage
4x150/70
Nominal diameter of complete cable mm
45
Nominal weight of cable kg/km
6730
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
4
Min. bending radius
During handling and installation, cable cm
54
In final installation, cable cm
38
During handling and installation, cable m
0.54
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116159
Reka code
1256669
4x185/95
Electric number
Size
Packaging
Voltage
4x185/95
Nominal diameter of complete cable mm
51
Nominal weight of cable kg/km
8492
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
4
Min. bending radius
During handling and installation, cable cm
61
In final installation, cable cm
43
During handling and installation, cable m
0.61
In final installation, cable m
0.43
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,193
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116173
Reka code
1256670
4x240/120
Electric number
Size
Packaging
Voltage
4x240/120
Nominal diameter of complete cable mm
56
Nominal weight of cable kg/km
11014
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
68
In final installation, cable cm
47
During handling and installation, cable m
0.68
In final installation, cable m
0.47
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,0754
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,153
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176116197
Reka code