FRHF / BFXI
Download product group datasheet
Fire-resistant power cable for fixed installations indoors and outdoors. Not to be laid in soil nor directly in cast concrete. For locations where safety requires the operation of alarm, control, signalling and energy circuits also during a fire. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. No requirement for CPR-classification.
Standards | HD 604 5 D, IEC 60502-1 |
---|---|
Conductor | 1,5-4 mm² circular solid copper, EN/IEC 60228 class 1 6-70 mm² circular stranded copper, EN/IEC 60228 class 2 |
Insulation | Cross-linked polyethylene XLPE and mica-tape |
Core Identification (all color combinations in the cable family) | 2x: Blue, brown 3x: Brown, black, grey 3G: Yellow-green, blue, brown 4G: Yellow-green, blue, brown, black (1,5 and 2,5 mm²) 4G: Yellow-green, brown, black, grey (4 mm² and above) 5G: Yellow-green, blue, brown, black, grey |
Inner covering | Extruded filling compound |
Oversheath | UV-protected polyolefin compound |
Colour of the oversheath | Orange |
2x1,5 N
Electric number
Size
Packaging
Voltage
2x1,5 N
Nominal diameter of complete cable mm
11
Nominal weight of cable kg/km
165
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
13
In final installation, cable cm
9
During handling and installation, cable m
0.13
In final installation, cable m
0.09
Max. pulling force
Pulling-eye kN
0.05
Pulling-stocking kN
0.06
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301708
Reka code
1146542
Nominal diameter of complete cable mm
11
Nominal weight of cable kg/km
165
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
13
In final installation, cable cm
9
During handling and installation, cable m
0.13
In final installation, cable m
0.09
Max. pulling force
Pulling-eye kN
0.05
Pulling-stocking kN
0.06
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301692
Reka code
1146542
2x2,5 N
Electric number
Size
Packaging
Voltage
2x2,5 N
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
200
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
14
In final installation, cable cm
10
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.08
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301739
Reka code
1146543
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
200
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
14
In final installation, cable cm
10
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.08
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301746
Reka code
1146543
2x4 N
Electric number
Size
Packaging
Voltage
2x4 N
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
254
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.12
Pulling-stocking kN
0.16
Resistance 20 °C Ω/km
4,61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301760
Reka code
1146544
2x6 N
Electric number
Size
Packaging
Voltage
2x6 N
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
339
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.18
Pulling-stocking kN
0.24
Resistance 20 °C Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301784
Reka code
1146545
3x1,5
Electric number
Size
Packaging
Voltage
3x1,5
Nominal diameter of complete cable mm
11
Nominal weight of cable kg/km
181
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
14
In final installation, cable cm
9
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.07
Pulling-stocking kN
0.09
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301814
Reka code
1146546
Nominal diameter of complete cable mm
11
Nominal weight of cable kg/km
181
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
14
In final installation, cable cm
9
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.07
Pulling-stocking kN
0.09
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301821
Reka code
1146546
3G1,5
Electric number
Size
Packaging
Voltage
3G1,5
Nominal diameter of complete cable mm
11
Nominal weight of cable kg/km
181
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
14
In final installation, cable cm
9
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.07
Pulling-stocking kN
0.09
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301869
Reka code
1146547
Nominal diameter of complete cable mm
11
Nominal weight of cable kg/km
181
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
14
In final installation, cable cm
9
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.07
Pulling-stocking kN
0.09
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301876
Reka code
1146547
Nominal diameter of complete cable mm
11
Nominal weight of cable kg/km
181
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
14
In final installation, cable cm
9
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.07
Pulling-stocking kN
0.09
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301852
Reka code
1146547
3G2,5
Electric number
Size
Packaging
Voltage
3G2,5
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
223
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
10
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.11
Pulling-stocking kN
0.15
Resistance 20 °C Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301913
Reka code
1146548
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
223
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
10
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.11
Pulling-stocking kN
0.15
Resistance 20 °C Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301906
Reka code
1146548
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
223
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
10
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.11
Pulling-stocking kN
0.15
Resistance 20 °C Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301890
Reka code
1146548
3G4
Electric number
Size
Packaging
Voltage
3G4
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
291
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.18
Pulling-stocking kN
0.24
Resistance 20 °C Ω/km
4,61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301920
Reka code
1146549
3G6
Electric number
Size
Packaging
Voltage
3G6
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
391
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
18
In final installation, cable cm
13
During handling and installation, cable m
0.18
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.27
Pulling-stocking kN
0.36
Resistance 20 °C Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301944
Reka code
1146550
3G10
Electric number
Size
Packaging
Voltage
3G10
Nominal diameter of complete cable mm
17
Nominal weight of cable kg/km
541
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
20
In final installation, cable cm
14
During handling and installation, cable m
0.2
In final installation, cable m
0.14
Max. pulling force
Pulling-eye kN
0.45
Pulling-stocking kN
0.6
Resistance 20 °C Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301968
Reka code
1146551
3G16
Electric number
Size
Packaging
Voltage
3G16
Nominal diameter of complete cable mm
19
Nominal weight of cable kg/km
758
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
23
In final installation, cable cm
16
During handling and installation, cable m
0.23
In final installation, cable m
0.16
Max. pulling force
Pulling-eye kN
0.72
Pulling-stocking kN
0.96
Resistance 20 °C Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176301982
Reka code
1146552
3G25
Electric number
Size
Packaging
Voltage
3G25
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
1172
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, cable cm
29
In final installation, cable cm
20
During handling and installation, cable m
0.28
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
1.13
Pulling-stocking kN
1.5
Resistance 20 °C Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302002
Reka code
1146553
3G35
Electric number
Size
Packaging
Voltage
3G35
Nominal diameter of complete cable mm
25
Nominal weight of cable kg/km
1514
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, cable cm
31
In final installation, cable cm
21
During handling and installation, cable m
0.31
In final installation, cable m
0.21
Max. pulling force
Pulling-eye kN
1.58
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302026
Reka code
1146554
3G50
Electric number
Size
Packaging
Voltage
3G50
Nominal diameter of complete cable mm
29
Nominal weight of cable kg/km
1993
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
3
Min. bending radius
During handling and installation, cable cm
35
In final installation, cable cm
24
During handling and installation, cable m
0.35
In final installation, cable m
0.24
Max. pulling force
Pulling-eye kN
2.25
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,387
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302040
Reka code
1146555
4G1,5
Electric number
Size
Packaging
Voltage
4G1,5
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
213
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
10
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.09
Pulling-stocking kN
0.12
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302071
Reka code
1146558
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
213
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
10
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.09
Pulling-stocking kN
0.12
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302088
Reka code
1146558
4G2,5
Electric number
Size
Packaging
Voltage
4G2,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
266
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.15
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302125
Reka code
1146559
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
266
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.15
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302118
Reka code
1146559
4G4
Electric number
Size
Packaging
Voltage
4G4
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
351
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.24
Pulling-stocking kN
0.32
Resistance 20 °C Ω/km
4,61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302149
Reka code
1146560
4G6
Electric number
Size
Packaging
Voltage
4G6
Nominal diameter of complete cable mm
16
Nominal weight of cable kg/km
473
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
20
In final installation, cable cm
14
During handling and installation, cable m
0.2
In final installation, cable m
0.14
Max. pulling force
Pulling-eye kN
0.36
Pulling-stocking kN
0.48
Resistance 20 °C Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302163
Reka code
1146561
4G10
Electric number
Size
Packaging
Voltage
4G10
Nominal diameter of complete cable mm
18
Nominal weight of cable kg/km
673
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
22
In final installation, cable cm
15
During handling and installation, cable m
0.22
In final installation, cable m
0.15
Max. pulling force
Pulling-eye kN
0.6
Pulling-stocking kN
0.8
Resistance 20 °C Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302187
Reka code
1146562
4G16
Electric number
Size
Packaging
Voltage
4G16
Nominal diameter of complete cable mm
21
Nominal weight of cable kg/km
949
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
25
In final installation, cable cm
18
During handling and installation, cable m
0.25
In final installation, cable m
0.18
Max. pulling force
Pulling-eye kN
0.96
Pulling-stocking kN
1.28
Resistance 20 °C Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302200
Reka code
1146563
4G25
Electric number
Size
Packaging
Voltage
4G25
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1489
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, cable cm
31
In final installation, cable cm
22
During handling and installation, cable m
0.31
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
1.5
Pulling-stocking kN
2
Resistance 20 °C Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302224
Reka code
1146564
4G35
Electric number
Size
Packaging
Voltage
4G35
Nominal diameter of complete cable mm
27
Nominal weight of cable kg/km
1854
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, cable cm
33
In final installation, cable cm
23
During handling and installation, cable m
0.33
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
2.1
Pulling-stocking kN
2.8
Resistance 20 °C Ω/km
0,524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302248
Reka code
1146565
4G50
Electric number
Size
Packaging
Voltage
4G50
Nominal diameter of complete cable mm
31
Nominal weight of cable kg/km
2472
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, cable cm
38
In final installation, cable cm
26
During handling and installation, cable m
0.38
In final installation, cable m
0.26
Max. pulling force
Pulling-eye kN
3
Pulling-stocking kN
4
Resistance 20 °C Ω/km
0,387
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302262
Reka code
1146566
5G1,5
Electric number
Size
Packaging
Voltage
5G1,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
244
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
5
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.11
Pulling-stocking kN
0.15
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302316
Reka code
1146569
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
244
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
5
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.11
Pulling-stocking kN
0.15
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302309
Reka code
1146569
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
244
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
5
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.11
Pulling-stocking kN
0.15
Resistance 20 °C Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302293
Reka code
1146569
5G2,5
Electric number
Size
Packaging
Voltage
5G2,5
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
314
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
5
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.19
Pulling-stocking kN
0.25
Resistance 20 °C Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302354
Reka code
1146570
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
314
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
5
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.19
Pulling-stocking kN
0.25
Resistance 20 °C Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302323
Reka code
1146570
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
314
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
5
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.19
Pulling-stocking kN
0.25
Resistance 20 °C Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302347
Reka code
1146570
5G4
Electric number
Size
Packaging
Voltage
5G4
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
417
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
5
Min. bending radius
During handling and installation, cable cm
19
In final installation, cable cm
13
During handling and installation, cable m
0.18
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.4
Resistance 20 °C Ω/km
4,61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302361
Reka code
1146571
5G6
Electric number
Size
Packaging
Voltage
5G6
Nominal diameter of complete cable mm
18
Nominal weight of cable kg/km
568
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
5
Min. bending radius
During handling and installation, cable cm
21
In final installation, cable cm
15
During handling and installation, cable m
0.21
In final installation, cable m
0.15
Max. pulling force
Pulling-eye kN
0.45
Pulling-stocking kN
0.6
Resistance 20 °C Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302385
Reka code
1146572
5G10
Electric number
Size
Packaging
Voltage
5G10
Nominal diameter of complete cable mm
20
Nominal weight of cable kg/km
807
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
5
Min. bending radius
During handling and installation, cable cm
24
In final installation, cable cm
17
During handling and installation, cable m
0.24
In final installation, cable m
0.17
Max. pulling force
Pulling-eye kN
0.75
Pulling-stocking kN
1
Resistance 20 °C Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302408
Reka code
1146573
5G16
Electric number
Size
Packaging
Voltage
5G16
Nominal diameter of complete cable mm
23
Nominal weight of cable kg/km
1156
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
5
Min. bending radius
During handling and installation, cable cm
28
In final installation, cable cm
19
During handling and installation, cable m
0.28
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
1.2
Pulling-stocking kN
1.6
Resistance 20 °C Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302422
Reka code
1146574
5G25
Electric number
Size
Packaging
Voltage
5G25
Nominal diameter of complete cable mm
29
Nominal weight of cable kg/km
1850
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
5
Min. bending radius
During handling and installation, cable cm
35
In final installation, cable cm
24
During handling and installation, cable m
0.35
In final installation, cable m
0.24
Max. pulling force
Pulling-eye kN
1.88
Pulling-stocking kN
2.5
Resistance 20 °C Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302446
Reka code
1146575
5G35
Electric number
Size
Packaging
Voltage
5G35
Nominal diameter of complete cable mm
31
Nominal weight of cable kg/km
2321
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
5
Min. bending radius
During handling and installation, cable cm
37
In final installation, cable cm
26
During handling and installation, cable m
0.37
In final installation, cable m
0.26
Max. pulling force
Pulling-eye kN
2.63
Pulling-stocking kN
3.5
Resistance 20 °C Ω/km
0,524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302460
Reka code
1146576
5G50
Electric number
Size
Packaging
Voltage
5G50
Nominal diameter of complete cable mm
35
Nominal weight of cable kg/km
3137
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
5
Min. bending radius
During handling and installation, cable cm
42
In final installation, cable cm
30
During handling and installation, cable m
0.42
In final installation, cable m
0.29
Max. pulling force
Pulling-eye kN
3.75
Pulling-stocking kN
5
Resistance 20 °C Ω/km
0,387
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176302484
Reka code
1146577