HXCMK 12/20 (24) kV 1-core Eca

Download product group datasheet

Medium-voltage cable for fixed installations indoors and outdoors. May be buried directly in soil. Installations must be in accordance with national regulations and rules of installations. The cable is flame-retardant according to CPR-class Eca.

Standards HD 620 10 F, SFS 5636
Reaction to fire Eca
CPR - DoP 2017076_DOP.pdf
Conductor Circular stranded copper, EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Inner covering Semiconducting tape
Metal screen Layer of helically wound copper wires with a counter helix copper tape
Oversheath UV-protected PVC compound
Colour of the oversheath Black

1x35/16

Electric number Size Packaging Voltage

1x35/16

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 902
Conductor material Copper
Nominal diameter of conductor mm 6.9
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 18.1
Number of wires 1
Nominal size of metal screen mm2 16
Min. bending radius
During handling and installation, cable cm 38
In final installation, cable cm 27
During handling and installation, cable m 0.38
In final installation, cable m 0.27
Max. pulling force
Pulling-eye kN 3.5
Pulling-stocking kN 0.7
Resistance 20 °C Ω/km 0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,2
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006030101
Reka code 1188221
Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 902
Conductor material Copper
Nominal diameter of conductor mm 6.9
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 18.1
Number of wires 1
Nominal size of metal screen mm2 16
Min. bending radius
During handling and installation, cable cm 38
In final installation, cable cm 27
During handling and installation, cable m 0.38
In final installation, cable m 0.27
Max. pulling force
Pulling-eye kN 3.5
Pulling-stocking kN 0.7
Resistance 20 °C Ω/km 0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,2
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006030095
Reka code 1188221