XCMK-HF / EXQJ / IFSI-Cu
Download product group datasheet
Copper power cable for fixed installations indoors and outdoors. May be buried directly in soil. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Dca-s2,d2,a2.
Standards | SFS 5546, SEK TS 424 14 18-1, HD 604 5 I & D, IEC 60502-1 |
---|---|
Reaction to fire | Dca-s2,d2,a2 |
CPR - DoP | 2021012_DOP.pdf |
Conductor | Circular solid copper, EN/IEC 60228 class 1 |
Insulation | Cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | Blue, brown Brown, black, grey Blue, brown, black, grey |
Inner covering | Extruded filling compound |
Metal screen | Copper wires and copper tape |
Oversheath | UV-protected polyolefin compound |
Colour of the oversheath | Black |
2x1,5/1,5
Electric number
Size
Packaging
Voltage
2x1,5/1,5
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
187
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
14
In final installation, cable cm
10
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.2
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011607
Reka code
1146105
2x2,5/2,5
Electric number
Size
Packaging
Voltage
2x2,5/2,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
235
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011614
Reka code
1146106
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
235
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176219393
Reka code
1146106
2x4/4
Electric number
Size
Packaging
Voltage
2x4/4
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
302
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.4
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
4,61
Maximum d.c. resistance at 20 °C, metal screen Ω/km
4,61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011621
Reka code
1146107
2x6/6
Electric number
Size
Packaging
Voltage
2x6/6
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
383
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
18
In final installation, cable cm
12
During handling and installation, cable m
0.18
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.6
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011638
Reka code
1146108
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
383
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable cm
18
In final installation, cable cm
12
During handling and installation, cable m
0.18
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.6
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029907
Reka code
1146108
3x1,5/1,5
Electric number
Size
Packaging
Voltage
3x1,5/1,5
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
205
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
10
During handling and installation, cable m
0.15
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.2
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023172
Reka code
1146225
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
205
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
15
In final installation, cable cm
10
During handling and installation, cable m
0.15
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.2
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023189
Reka code
1146225
3x2,5/2,5
Electric number
Size
Packaging
Voltage
3x2,5/2,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
254
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.4
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023202
Reka code
1146226
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
254
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.4
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023196
Reka code
1146226
3x4/4
Electric number
Size
Packaging
Voltage
3x4/4
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
338
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.6
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
4,61
Maximum d.c. resistance at 20 °C, metal screen Ω/km
4,61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011706
Reka code
1146227
3x6/6
Electric number
Size
Packaging
Voltage
3x6/6
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
437
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
19
In final installation, cable cm
13
During handling and installation, cable m
0.18
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.9
Pulling-stocking kN
0.3
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023257
Reka code
1146228
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
437
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable cm
19
In final installation, cable cm
13
During handling and installation, cable m
0.18
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.9
Pulling-stocking kN
0.3
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023301
Reka code
1146228
4x1,5/1,5
Electric number
Size
Packaging
Voltage
4x1,5/1,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
230
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023615
Reka code
1146305
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
230
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12,1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023622
Reka code
1146305
4x2,5/2,5
Electric number
Size
Packaging
Voltage
4x2,5/2,5
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
292
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.5
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023639
Reka code
1146306
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
292
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.5
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7,41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023646
Reka code
1146306
4x4/4
Electric number
Size
Packaging
Voltage
4x4/4
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
393
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
18
In final installation, cable cm
13
During handling and installation, cable m
0.18
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.8
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
4,61
Maximum d.c. resistance at 20 °C, metal screen Ω/km
4,61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011850
Reka code
1146307
4x6/6
Electric number
Size
Packaging
Voltage
4x6/6
Nominal diameter of complete cable mm
17
Nominal weight of cable kg/km
521
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
20
In final installation, cable cm
14
During handling and installation, cable m
0.2
In final installation, cable m
0.14
Max. pulling force
Pulling-eye kN
1.2
Pulling-stocking kN
0.4
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023004
Reka code
1146308
Nominal diameter of complete cable mm
17
Nominal weight of cable kg/km
521
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable cm
20
In final installation, cable cm
14
During handling and installation, cable m
0.2
In final installation, cable m
0.14
Max. pulling force
Pulling-eye kN
1.2
Pulling-stocking kN
0.4
Resistance 20 °C Ω/km
3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3,08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023219
Reka code
1146308